20

23

Maintained Keyswitch 
Arm

A keyswitch module may be connected to the zone programmed as Maintained Keyswitch arm. In the restored state, the 
panel is disarmed. Only the violation of this zone type to the alarm state will make the panel arm. Tampers and Faults will 
only initiate their respective trouble sequence.

NOTE: The panel arms in Away mode (for SKAFOR Installations only).

24

Future Use

25

Interior Delay Zone

The Interior Delay Zone is normally used with motion detectors and has a standard exit delay time. If the panel is armed, and 
a Delay zone is violated during the Exit Delay (or the Away function key is used), the Interior Delay Zone will be active at the 
end of the Exit Delay. This zone will cause an instant alarm when violated. This zone type will follow the Entry Delay time 
provided that a Delay zone is violated first. If the panel is armed, and a Delay zone is NOT violated during the Exit Delay (or 
the Stay function key is used, or [*][9] armed), a violation of this zone type will initiate Entry Delay1.

26

24-hr Non-Alarm

These zones are active at all times but do not cause an alarm, and do not show up in alarm memory. Zone Attributes such as 
Zone Bypassing and Door Chime affect the functionality of this zone. A 24 Hour Non-alarm zone may be used for Zone Fol-
lower automation applications.

NOTE: This zone type will be active in Walk Test. Tampers and Faults. Zones programmed as 24 Hour Non-alarm 
type will not cause alarms.  NOTE: Alarms on this zone will not initiate Downlook.

27

Future Use

28

Future Use

29

Auto Verified Fire Zone 

This zone ensures that an alarm condition persists by resetting a tripped sensor in a fire zone and confirming that the sensor 
has remained tripped or is waiting for the sensor to re-trip within a set period of time. (e.g. Cycling power to a smoke detec-
tor to ensure the condition persists when power is restored.) The alarm sequence for the zone is indicated below:
    Step #1                       Duration 20 Seconds                    Sensor Reset
    Step #2                       Duration 10 Seconds                    Settle Time (Power Up)
    Step #3                       Duration 60 Seconds                    Check for Verified Alarm

NOTE: If another fire device detects fire during the Auto Verify or Delay sequence, the sequence is  terminated 
and alarms are immediately generated for all pending zones. This applies to all other Fire zones on the system 
regardless of the partition assignments (i.e. two fire alarms anywhere on the system will cancel all pending fire 
delays and create immediate alarms).

30

Fire Supervisory Zone

When this zone is violated, the system turns on the keypad buzzer, and communicates the supervisory alarm condition to 
the monitoring station. The buzzer will not follow the Bell-Time-Out timer. To silence the buzzer, a valid access code must be 
entered.

31

Day Zone

A zone programmed with this type has different characteristics in the armed and disarmed state. In the disarmed state, vio-
lating this zone will sound the keypad buzzer but will not log or report the event. In the armed state, violating this zone will 
sound the bell and communicate the event.

32

Instant, Stay/Away 
Zone

The Instant Stay/Away Zone will be bypassed when armed in the Stay Mode, but will act like an Instant Zone when armed in 
the Away Mode. This zone type is useful for motion detectors in an installation that must not follow the Entry Delay after a 
Delay zone is violated, but must still retain the Stay/Away functionality.  

33

Push to Set Zone

When the panel is armed with this zone type programmed an infinite exit delay will begin (see chart below). To complete the 
arming sequence after infinite exit delay has begun, the Push to Set zone must be violated and restored, the system then 
counts down a five second exit delay. The infinite exit delay is audible.
All arming methods that start infinite exit delay are audible except and [*][9] arming.  This zone definition uses SIA data 
code “BA-XX / BH-XX” when violated during walk test, Exit Delay Termination should not be used with this zone type 
because it does not go into alarm while armed or disarmed (where XX is the zone that went into alarm). Away arming with 
a bypassed Push to Set or Final Door Set zone prevents the panel from arming because the exit delay never terminates.

34

Final Door Set Zone

If Final Door Set zone type is programmed, infinite exit delay will commence when arming is initiated.  To complete the arm-
ing sequence after infinite exit delay has begun, the Final Door Set zone must be violated and then restored.  When the sys-
tem is armed, this zone functions identically to a Delay 01 zone, including the entry delay programmed in Section [005]. 
Away arming with a bypassed Push to Set zone or Final Door Set will prevent the panel from arming because the exit delay 
never terminates.

35

24-hr Bell/Buzzer 

Similar to  24 Hour Burglary Zone when armed. Similar to  24 Hour Supervisory Buzzer zone when disarmed.  When the 
panel is armed and this zone is violated, the Bell will sound for the duration of Bell Time Out.  When the panel is disarmed 
and this zone is violated, the buzzers will sound until a valid access code is entered. The SIA identifier BA-XX/BH-XX will be 
sent for this zone type in both states.

36

24-hr Non-Latching 
Tamper Zone

To provide support for tamper protection this new 24-hr Non-Latching Tamper Zone type is implemented. This zone is 
always active and will report a tamper condition if the panel is armed or disarmed.

37

Night Zone

This zone type will only be considered as armed when the panel is armed in one of the following ways:
1 The panel is armed and then a delay zone is activated during an exit delay
2 The panel is armed using the away mode function key on the keypad or wireless key.
If the panel is stay armed and then the interior zones are activated through *1 the night zones will not be armed. Instead 
the zone will act like a interior stay away type zone.  This will give the user a way of arming an area that will not be used 
during the night.

87

Delayed 24-hr Fire 
(Wireless)

Used only with wireless smoke detectors. Functions same as that of Zone Type [07].

88

Standard 24-hr Fire 
(Wireless) 

Used only with wireless smoke detectors. Functions same as that of Zone Type [08].

Option

Zone Type

Description

UK

Arming Method

Infinite 

Exit Delay

Arming 

Mode

Arming Method

Infinite 

Exit Delay

Arming 

Mode

Arming Method

Infinite 

Exit Delay

Arming 

Mode

User Code

Y

Away

[*][0] Arm

Y

Away

Wireless Key Stay

N

Stay

Key Switch

Y

Away

Escort Local

Y

Away

Escort Remote

N

Away

Away Arm

Y

Away

[*][9] Arm

N

Stay

DLS Arm

N

Away

Wireless Key Away

Y

Away

Stay Key

N

Stay

Auto Arm

N

Away

UK

IMQ

Summary of Contents for PC1616

Page 1: ...gher PC1616 PC1832 PC1864 This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer The entire manual sh...

Page 2: ...bus Terminals RED BLK YEL GRN 6 Programmable Outputs PGM1 to PGM4 6 Zone Input Terminals Z1 to Z8 6 Telephone Connection Terminals TIP RING T 1 R 1 6 2 3 Wire Routing for Power Non Power Limited 6 2 4...

Page 3: ...one Assignments 35 Partitions and Zone Assignment 35 5 5 Communicator Programming 35 Communicator Telephone Numbers 35 301 First Telephone Number 35 302 Second Telephone Number 35 303 Third Telephone...

Page 4: ...toring 51 6 1 Partitions and Fire System Configuration 51 Fire Configuration 1 51 Fire Configuration 2 51 6 2 Fire Zones 51 Standard Fire Operation 51 Auto Verify Fire 51 Four Wire Smoke Detector Zone...

Page 5: ...your programming Be sure to record all your system programming in the Programming Worksheets If adding modules to your PowerSeries Control Panel refer to the Installation Instructions that come with...

Page 6: ...upervision for loss of primary power source AC Fail battery fail or battery low voltage Battery Trouble with indication provided on the keypad Internal clock locked to AC power frequency Operating Env...

Page 7: ...etails NOTE Only the first 32 zones on the PC1616 PC1832 PC1864 system can be used as wireless zones NOTE PC1616 expandable to 16 zones only PC5200 Power Supply Output Module The PC5200 can provide up...

Page 8: ...with removable door UL ULC Household Fire ULC Commercial Burglary Made with 22Ga steel Approximate Dimensions 287mm x 297mm x 76mm 11 3 x 11 7 x 3 0 PC5003C Hinged Door Description Main Control Cabine...

Page 9: ...ete description of how to pro gram the panel Section 5 0 contains complete descriptions of the various programmable features what options are available and how the options function The Programming Wor...

Page 10: ...inimum 6 4mm separation must be maintained at all points between power limited and non power limited wiring and connections NOTE Wire entry for power limited wiring must be sepa rated by a different e...

Page 11: ...t enter 0 for Global operation or enter 1 8 for Partitions 1 8 2nd digit enter 1 to 8 for Slot Assignment 5 Press the key twice to exit programming 6 Continue this procedure at each keypad until all h...

Page 12: ...matically search for all modules connected to the system for the next 60 seconds Do not perform any other oper ations during this 60 second period 6 Once the search is complete enter section 903 to co...

Page 13: ...ions for DEOL End of Line Resistors Section 013 Option 1 Double End of Line Resistors Section 013 Option 2 Fire Zone Wiring 4 wire Smoke Detectors All zones defined as Fire see section 5 2 Basic Progr...

Page 14: ...ngle End of Line and Double End of Line To connect the PGM output on a PK55XX RFK55XX key pad run one wire to the Z P terminal and the other to R PK55XX RFK55XX NOTE End of line resistors must be plac...

Page 15: ...ter the corresponding HEX digit 1 A 2 B 3 C 4 D 5 E 6 F After the correct HEX digit is entered the Ready light will continue to flash If another HEX digit is required press the corresponding number If...

Page 16: ...hrough the entry exit door the panel will bypass all Stay Away type zones The panel is now Stay armed The Bypass light will remain on to inform the home owner that the interior protection is bypassed...

Page 17: ...d The keypad will display Zone Search Zone Name 3 Enter the two digit number of the zone s to be bypassed 01 64 You can also use the keys to find the zone to be bypassed and then press to select the z...

Page 18: ...C5400 Printer module has a fault and is off line or T Link Troubles Users can view specific conditions in the Event Buffer Light 4 General System Tamper Tamper has been detected from a module Light 5...

Page 19: ...rtition number 1 8 to toggle it on or off NOTE Partition programming is NOT supported by the fol lowing keypads PC5508 Z PC5516 Z PC5532 Z versions v2 00 and lower LCD5500 Z version 2 x and lower LCD5...

Page 20: ...tempt to call the downloading computer NOTE The downloading computer must be waiting for the panel to call before downloading can be performed 7 For Future Use 8 User Walk Test 6 User Functions allows...

Page 21: ...xit delay The Quick Arm feature must be enabled for this key to function Section 015 Option 4 If Quick Arming is not enabled the user must enter their access code after pressing the function key in or...

Page 22: ...selected the Trouble light will turn on if a trouble con dition is present and the Armed light will turn on if all the partitions are armed To select a partition the user must press and hold one of k...

Page 23: ...and transmission by the communicator is delayed by 30 seconds If the alarm is acknowledged by pressing any key within 30 seconds the bells will silence and the transmission will be aborted If the ala...

Page 24: ...armed in the Away Mode This zone type is useful for motion detectors in an installation that must not follow the Entry Delay after a Delay zone is violated but must still retain the Stay Away function...

Page 25: ...ing Code Section 349 Bell Circuit Trouble Restoral Reporting Code Section 350 Temporal Three Fire Signal Enable Disable Section 013 Option 8 Fire Bell Continuous Section 014 Option 8 006 Installer s C...

Page 26: ...e exit delay begins 07 Keypad Buzzer Follow This output will activate switch to ground when any of the following events occur and will remain active for as long as the keypad buzzer is active Door Chi...

Page 27: ...PGM type will activate 22 Command Output 4 This output is activated by entering the 7 4 command The configuration of the corresponding attributes deter mines how this PGM type will activate 23 Silent...

Page 28: ...ication of alarms and the initiation of the confirmation time the toggle option TX Delay During Entry Only must be enabled The transmission delay attribute must also be enabled for all zones and the c...

Page 29: ...emory the bell will emit a series of three squawk pairs to indicate the alarm memory NOTE If you enable the Bell Squawk on Arming Disarming the bell will sound arm disarm bell squawks for all access c...

Page 30: ...call direc tion options Fire Auxiliary and Panic key NOTE The Fire Auxiliary Panic keys will operate even if Keypad Blanking and Keypad Lockout are active See Section 5 3 Basic Programming PWS Sect 3...

Page 31: ...ave Mode ON Power Save Mode Enabled If AC power fails all keypad lights including backlighting will be shut OFF The keypad lights will come back ON after a keypress Entry delay Audible Alarm or keypad...

Page 32: ...the Auto arm and Test Transmissions programming OFF Daylight Savings Time Disabled The panel will make no automatic time adjustments for Daylight Sav ings time 7 For Future Use 8 Bell Squawk on Away A...

Page 33: ...larm when faulted while stay armed Zone types 9 24 Hour Supervisory 12 24 Hour Hold Up 26 24 Hour Non Alarm do not generate an audible alarm in any armed state stay or away OFF Wireless Zone Fault Doe...

Page 34: ...try Procedure The following zone type alarms will follow bell delay if a zone violation occurs while entry delay is active on the partition Instant Interior Interior Stay Away Delay Stay Away 24 Hr Su...

Page 35: ...not be locked out after an alarm occurs 5 Engineer s Reset ON Engineer s Reset Enabled If the panel has gone into alarm during the previous armed period or if a 24 Hour alarm has occurred armed or dis...

Page 36: ...ate tamper alarms The panel will generate a silent trouble NO trouble beeps but the Trouble LED is turned ON called RF Device Delinquency that s only viewable in 2 Trouble Mem ory The user can overrid...

Page 37: ...e system trouble beeps will not be sounded at the keypad OFF Trouble Beeps will Sound Every 10 Seconds When a trouble is detected on the system trouble beeps will be sounded at the keypad NOTE This op...

Page 38: ...ll not log or transmit If a second zone is violated within the Cross Zone Timer s seconds duration the panel will go into the appropriate alarm sequence and will communicate both zone alarms No Police...

Page 39: ...233 Partition 5 Zone Assignments Sections 234 to 241 Partition 6 Zone Assignments Sections 242 to 249 Partition 7 Zone Assignments Sections 250 to 257 Partition 8 Zone Assignments Sections 258 to 265...

Page 40: ...ral Reporting Codes Zones 1 to 64 If the Restoral on Bell Timeout option is selected the panel will send the Zone Restoral Reporting Code for the zone when the alarm output times out AND the zone is s...

Page 41: ...o Arm Cancellation This reporting code is transmitted when the Auto Arming sequence is canceled or Postponed Special Opening A Special Opening Reporting Code will be transmitted if the Partition s is...

Page 42: ...eporting Code in place of the standard Peri odic Test Transmission if any of the following conditions exist Fire Zone Trouble Zones 1 64 Battery Trouble PC1616 PC1832 PC1864 PC520X Fire Zone Alarm Zon...

Page 43: ...med as 00 the panel would not report If the SIA Sends Automatic Reporting Codes option is dis abled the panel will operate as follows 1 If the reporting code for an event is programmed as 00 or FF the...

Page 44: ...mple If you program the zone 3 alarm reporting code as 31 the panel will send event code 1 in channel 3 The panel will send the number 5 for each of the other channels so that the event code will look...

Page 45: ...tores This value defines the number of attempts alarm and restore pairs per zone that the panel will log and communicate before it shuts down for that zone swinger shutdown Valid entries are 000 to 01...

Page 46: ...his interval is in minutes or days is determined on Section 702 Option 3 NOTE If using Test Transmission Exception a value of 001 will disable the Test Transmission Exception feature Wireless Zone Low...

Page 47: ...y armed Activity on Bypassed zones does not affect this timer The timer is reset on arming OFF Delinquency Follows Arming Closing Delinquency This reporting code is sent whenever the programmed number...

Page 48: ...2 Walk Test Communication ON Zone Alarms Communicate during Walk Test Enabled Zone alarms that occur during Walk Test will communicate if programmed to do so OFF Zone Alarms Communicate during Walk T...

Page 49: ...will be busy for the duration of the PC Link connection The status LEDs will display the current system status on the keypad where the PC Link was initiated For more information on connect ing the PC...

Page 50: ...sheets for the PGM output types defaults CAUTION Select the normal and active states of each PGM output to ensure that undesirable output states do not occur after a loss and restore of AC power If yo...

Page 51: ...Trouble 8 Loss of Clock Loss of Time Trouble PGM Output Types 10 System Event 1 Burglary Delay Instant Interior Stay Away and 24 Hour Burg Zone Types 2 Fire F Key Fire Zone 3 Panic P Key and Panic zon...

Page 52: ...l access codes on the system will be 4 digits in length For any existing codes the last 2 digits are removed 6 Busy Tone ON Busy Tone Detection Enabled If these tones are detected the communicator wil...

Page 53: ...n 901 Zones do not have to be restored to stop the test After the test is complete check the Event Buffer to ensure that the Audible Silent 24 hr PGM alarms have been restored NOTE The Alarm Memory is...

Page 54: ...section 991 again 993 999 Factory Defaults On occasion it may be necessary to default the main control panel or one of the modules that can be connected There are several different defaults available...

Page 55: ...stor this will be indicated as a Zone Trouble Ground Fault resistance 40k to earth ground indicated as a Ground Fault Trouble on PC5700 zone 7 Typical Fire Devices used on this zone type are Heat Dete...

Page 56: ...entering 7 2 in order to reset smoke detectors Subsequent Alarm Operation If the alarm notification appliances have been silenced manually or automatically and a subsequent fire alarm is initiated the...

Page 57: ...ire Keys on any keypad are pressed for two seconds NOTE For commercial applications do not program the F key for keypads that are readily accessible by the public For more information regarding this k...

Page 58: ...pro grammed as not bypassable Casual Users The installer should caution the user s not to give system information to casual users e g codes bypass methods etc to baby sitters or service people Only th...

Page 59: ...Cancel Annunciation 328 8th entry Access to the reporting code for Alarm Cancelled Annunciate that a Cancel was transmitted Default Enabled Required Duress Feature 5 Master Code 33rd and 34th entries...

Page 60: ...ed A R 4 A6 BC 00 329 F Key Alarm Rest Keypad fire alarm alarm and restore rep codes sent together A R 1 15 FA 00 FH 00 329 A Key Alarm Rest Keypad auxiliary alarm alarm and restore rep codes sent tog...

Page 61: ...e TLM Trouble Restore occurs on the PC5700 MA R 3 52 LR XX A R alarms restorals T R tampers restorals O C openings closings MA R miscellaneous alarms restorals T test transmissions UU user number user...

Page 62: ...e power from the control panel must be UL Listed for the intended application and operate over the range of 11 6 12 6VDC residential 12 0VDC commercial The DSC Bravo Series are recommended UL Listed m...

Page 63: ...rsons b The connection to the mains supply must be made as per the local authorities rules and regulations An appropriate disconnect device must be provided as part of the building installation Where...

Page 64: ...tion WARNING High Voltage Disconnect AC Power and telephone lines before servicing WARNING 220 240V 50 60Hz 200mA AC PC5003C Cabinet Shown Use Model Power UC1 for 2 Battery Installations CON1 BAT BAT...

Page 65: ...ual NOTE Do not combine the 2 wire smoke detector and 4 wire smoke detector on PGM2 only 2 wire smoke detectors on PGM2 SMOKE DETECTOR POWER 12 VDC IN OUT NO ALM OUT IN BLK WHT RED GRN LATCHING 4 WIRE...

Page 66: ...International Programming 47 K Key 26 Key Annunciation 26 Keybus Fault 29 Keypad Assignment 7 Keypad Blanking 27 Keypad Buzzer Follow 22 Keypad Commands 12 Keypad Lockout 24 Keypad Lockout Options 24...

Page 67: ...It is important that a security system be reviewed periodically to ensure that its features remain effective and that it be updated or replaced if it is found that it does not pro vide the protection...

Page 68: ...ill notify you in advance that temporary discontinuance of service may be required But if advance notice is not practical the Telephone Company will notify the customer as soon as possible Also you wi...

Reviews: