B.1 PC1616/PC1832/PC1864 UL/ULC Wiring Diagram
A p p e n d i x B : W i r i n g D i a g r a m s
Compati
bl
e
System Ke ypad s
F
or Fire/Bel
l
wi r ing, re f er t
o
Re f erence Ma
n
ual
Bell/Siren
700mA (max)
Obse r ve
P
olarit
y.
120V
AC
/60Hz
Primary
16.5V
AC
/40VA
NOTE:
Battery capacity for 4h standby is at least
4Ah. Battery capacity for 24h standby is 14Ah (Max.
Aux current must not exceed 480mA). Recommended
Batteries: DSC BD4-12 or DSC BD7-12.
12V 4.0Ah/7Ah
12V 7Ah
RJ-31X Telephone
Plug 26 AWG
Maximum battery
charge current
is 400mA
AUX+
PGM2
2k2
EOLR
10ohm
0.5 W
Normally Open
Push-button Switch
AUX INPUT
WIRING
TYPICAL ZONE CIRCUITS
RESISTOR
IDENTIFICATIONS
2-WIRE SMOKE
BELL CIRCUIT
SINGLE ZONE EOL
AUX INPUT
Smoke detector must be latching type (ex. DSC FSA-410B Series)
To reset smoke detector, enter [
✱
][7][2]
4-WIRE SMOKE DETECTORS
NOTE:
Refer to Installation Manual & Smoke
Detector Instruction Sheet when locating detectors.
35mA
max.
Class 2 Transformer
Model DSC PTD1640V
SIA-FAR Minimum System Requirements:
1 PC1616/1832/1864 Panel
2 Local annunciation devices
Local annunciation devices may be
any combination of these keypads:
LCD5500Z, LCD5501Z, PKP-LCD, PKP-ICN
220
POWER LIMITED
POWER LIMITED
2-WIRE SMOKE DETECTORS
DO NOT
combine different models on the same circuit
as operation may be impaired.
Ground wire from
building electrical
installation
NOTE: For ULC fire monitoring, please refer to the PC5700 Installation Instructions
PGM CONNECTIONS
IMPORTANT: Minimum 6.4mm (1/4”)
separation must be maintained between
RM-1 circuits and all other wiring
Temperature Range: 0°C-49°C [32°F-120°F] / Maximum
Humidity: 85% R.H.
For detailed installation and operating instructions, refer to
the Installation Guide #29007109, User Manual #29007165
and the Reference Manual #29007160 (available on the DSC
website). The PC1616/PC1832/PC1864 is UL Listed for
limited energy installations per NEC Article 760. Recognized
limited energy cable should be used. Observe NEC wiring
requirements and local codes defined by the authority having
jurisdiction. Security detection devices that require power
from the control panel must be UL Listed for the intended
application and operate over the range of 11.6-12.6VDC
(residential), 12.0VDC (commercial). The DSC Bravo Series
are recommended UL Listed motion detectors. Compatible
system keypads: PC5508Z/KP5508Z, PC5516Z/KP5516Z,
PC5532Z/KP5532Z. LCD5500Z/KP5500Z, LCD5501, PKP-
LCD, PKP-ICN, LCD5501Z32-433.
This device complies with Parts 15 and 68 of the FCC rules. Operation
is subject to the following 2 conditions: [1] this device may not cause
harmful interference and [2] this device must accept any interference
received, including interference that may cause undesired operation.
Model: PC1864 FCC Reg. No. F53AL01BPC1864
Model: PC1832 FCC Reg. No. F53AL01BPC1832
Model: PC1616 FCC Reg. No. F53AL01BPC1614
REN = 0.1B Plug Type: RJ-31X MADE IN CANADA
ULC NOTES
• For ULC Listed Fire Monitoring Installations &
module requirements, please refer to the ULC
Installation Information Sheet, part #29002157.
• Use a CSA/cUL transformer, hardwired.
• All tamper circuits may be connected to the same
zone.
• Use ULC-LA for AC Power indication.
(a) The delay (power-up) time marked on the installation wiring diagram of the smoke detector or on the
installed smoke detector(s) is to be used.
*AUX Wiring
Use No.14-22 AWG conductor
AUX+ and Keybus (RED) are internally
connected. Total current draw from
keypads, PGM Outputs and AUX
circuits must not exceed 700mA.
NOTE:
Do not connect
transformer to a
receptable controlled
by a switch.
700mA*
(see Aux
note above)
PC18-1
FSA-210B Series
NOTE:
Refer to the FSA-210 Installation Manual for more details.
PC1616/PC1832/PC1864 UL/ULC Wiring Diagram
NAME
MODEL
MAX #
BASE
COMPATABILITY ID
DSC
NONE
FS200
SEE NOTE
Control panel is suitable for the following UL installations: (1)
Grade AA Central Station and Grade AA
Police Connect with high line security (using T-LINK to communicate to the Sur-Gard MLR-IP Receiver). (2)
Household Fire and Grade A Household Burglary and Home Health Care Signaling Equipment (3) Grade
A Local I Grade B Central Station and Police Connect with basic line security (4) Grade C Central Station.
Refer to Installation Manual
ULC-LA
NOTE:
For ULC installations, please refer to the ULC Wiring Diagram part#18006238 and the ULC Installation Information Sheet part#29002157.