43
[381] - Second Communicator Option Codes
2
Restore Transmission
ON
Restore Transmissions on Bell-Time-out
Zone restore reporting codes will not be transmitted
until the zone has been restored and the Bell cut-off time has expired. If the zone is not restored
when the bell cut-off time expires, the restore will be transmitted when the zone physically restores
or when the system is disarmed.
NOTE: 24-hour zones will not restore until the zone is physically restored.
OFF
Restore Transmissions Follow Zones
Zone restore reporting codes will be transmitted when the
zone is physically restored. If the zones are still active when the system is disarmed, the restore codes
will be transmitted when the system is disarmed.
NOTE: 24-hour zones will not restore until the zone is physically restored.
3
Dialing Method
ON
Pulse Dialing enabled
The control panel will dial telephone numbers using pulse (rotary) dialing.
OFF
DTMF Dialing enabled
The control panel will dial telephone numbers using DTMF (dual tone multi-
frequency) dialing.
4
Switch to Pulse Dialing
ON
Switch to Pulse Dialing after 4 DTMF attempts
If DTMF dialing is enabled, the control panel will
dial telephone numbers using DTMF dialing for the first 4 attempts. If unsuccessful, the control
panel will switch to pulse (rotary) dialing for the remaining attempts.
OFF
DTMF Dial for all Attempts
If DTMF dialing is enabled, the control panel will dial telephone num-
bers using DTMF dialing for all dialing attempts.
5
3rd Phone Number Enable
ON
3rd Phone Number Enabled
The 3rd Phone number will be used for Alternate Dialing with the 1st
Phone Number or as a Backup of the 1st Phone Number (see light 6).
OFF
3rd Phone Number Disabled
The 3rd Phone number will not be used.
6
3rd Phone Number
ON
Alternate Dialing Enabled (1st & 3rd)
After each dialing attempt, the communicator switches
between the 1st Phone Number and 3rd Phone Number.
OFF
Call 1st Number, Backup to 3rd Number
If the programmed number of attempts to communicate
to the First Telephone Number fail, The same number of attempts will be made to communicate to
the Third Telephone Number. If all attempts to communicate to the Third Telephone Number fail, a
Failure to Communicate Trouble will be generated.
7
For Future Use
8
Delinquency
ON
Delinquency Follows Zone Activity (Activity Delinquency)
This feature assists in the monitoring
of the elderly and the handicapped. If there is no zone activity on a partition, the Delinquency Trans-
mission Delay timer in Section [377] will begin counting in hours. When the counter reaches the pro-
grammed time, the panel will communicate the Delinquency Code to the central station, if
programmed. If there is zone activity present on the system at any time, the counter will be reset. If
this option is used, the Closing Delinquency option is not available.
NOTE: This code will not be transmitted for partitions that are “Away” armed. Activity on
Bypassed zones does not affect this timer. The timer is reset on arming.
OFF
Delinquency Follows Arming (Closing Delinquency)
This reporting code is sent whenever the
programmed number of days for Delinquency has expired without the partition being Armed. The
timer for this feature is programmed in Section [377]. The value programmed in this section deter-
mines the number of days the partition counts when not being armed before sending the Delin-
quency reporting code to the central station. Once this code is sent, the timer will not be started
again until the partition has been armed. Each day programmed in the counter represents one day
PLUS the time it takes for the partition to reach midnight. This feature may disabled by program-
ming 000 in Section [377].
Option
Communicator Code
On/Off
Description
Option
Communicator Code
On/Off
Description
1
Opening After Alarm Keypad
Ringback
ON
Opening After Alarm Keypad Ringback Enabled
When the Opening After Alarm reporting code
is successfully transmitted to a programmed telephone number, the keypad will sound a series of 8
beeps to confirm to the end user that the Opening After Alarm Code was sent and received. This
Ringback will occur for each Opening After Alarm code successfully reported.
OFF
Opening After Alarm Keypad Ringback Disabled
When the Opening After Alarm reporting
code is successfully transmitted to a programmed telephone number, the keypad will not sound
ringback.
2
Opening After Alarm Bell
Ringback
ON
Opening After Alarm Bell Ringback Enabled
. When the Opening After Alarm reporting code is
successfully transmitted to a programmed telephone number, the Bell will sound a series of 8
squawks to confirm to the end user that the Opening After Alarm Code was sent and received. This
Ringback will occur for each Opening After Alarm code successfully transmitted.
OFF
Opening After Alarm Bell Ringback Disabled
When the Opening After Alarm reporting code is
successfully transmitted the system will not perform a ringback.
3
SIA Reporting Codes
ON
SIA Sends Programmed Rep. Codes
This option is for use with the SIA communication format.). If
00 is programmed in the reporting code section, the event will not be communicated. When this
option is ON and there is a valid reporting code programmed in the reporting code section, the pro-
grammed reporting code will be transmitted. If FF is programmed as a reporting code, the event will
not be communicated.
Reporting Code Entry Option ON Option OFF
00 No Transmission No Transmission
FF No Transmission Auto Rep Code sent
01-FE 01-FE sent Auto Rep Code sent
NOTE: If the automatic SIA or automatic Contact ID reporting formats are not used, report-
ing codes must be programmed.
OFF
SIA Sends Automatic Rep. Codes
When this option is OFF and there is a valid reporting code (01-
FE) or FF programmed in the reporting code section, the panel will transmit an automatic reporting
code for SIA only. This would be used when automatic reporting codes are required but there is a
requirement for a different reporting code (i.e. Pager Format, etc.).