9
The following chart shows zone status under certain condi-
tions for NC Loops:
Normally Closed Loops . . . . . . . . . . . . . . Section [013], Option [1]
Single End Of Line (EOL) Resistors
To enable panel detection of single end-of-line resistors, pro-
gram section [013], options [1] and [2] to OFF.
NOTE:
This option should be selected if either Normally
Closed (NC) or Normally Open (NO) detection devices or con-
tacts are being used
.
The following chart shows zone status under certain condi-
tions for SEOL:
End of Line Resistors . . . . . . . . . . . . . . . . Section [013], Option [1]
Single End of Line Resistors . . . . . . . . . . . Section [013], Option [2]
Double End of Line (DEOL) Resistors
Double End of Line resistors allow the panel to determine if
the zone is in alarm, tampered or faulted.
To enable panel detection of double end of line resistors, pro-
gram section [013], option [1] to OFF and option [2] to ON.
NOTE:
If the Double EOL supervision option is enabled, all
hardwired zones must be wired for Double EOL resistors,
except for Fire and 24 Hour Supervisory zones. Do not use
DEOL resistors for Fire zones or 24 Hour Supervisory zones.
NOTE:
Do not wire Fire zones to keypad zone terminals if
the DEOL supervision option is selected.
NOTE:
This option can only be selected if Normally Closed
(NC) detection devices or contacts are being used. Only one
NC contact can be connected to each zone.
The following chart shows zone status under certain condi-
tions for DEOL:
End-of-Line Resistors . . . . . . . . . . . . . . . . Section [013], Option [1]
Double End-of-Line Resistors . . . . . . . . . . Section [013], Option [2]
Fire Zone Wiring - 4-wire Smoke Detectors
All zones defined as Fire (see section 5.2 ’Basic Program-
ming’ ) must be wired according to the following diagram:
For a complete description of how fire zones operate, see
section 5.2 ’Basic Programming’ sections [001]-[004] option
07 and 08.
NOTE:
Smoke detectors must be latching type. To reset
smoke detector, enter [*][7][2].
Compatible 4-Wire Smoke Detectors
Fire Zone Wiring - 2-wire Smoke Detectors
If PGM 2 has been programmed for 2-Wire Smoke Detector
connection (see section 5.2 ’Basic Programming’ ) , the
detectors must be wired according to the following diagram:
For a complete description of how fire zones operate, see
section 5.2 ’Basic Programming’ section [009] option 04.
NOTE:
Do not combine models from different manufactur-
ers on the same circuit. Operation may be impaired.
NOTE:
Refer to smoke detector installation sheet when posi-
tioning detectors.
Loop Resistance
Loop Status
0
Ω
(shorted wire, loop shorted)
Secure
Infinite (broken wire, loop open)
Violated
Loop Resistance
Loop Status
0
Ω
(shorted wire, loop shorted)
Violated
5600
Ω
(contact closed)
Secure
Infinite (broken wire, loop open)
Violated
Loop Resistance
Loop Status
0
Ω
(shorted wire, loop shorted)
Fault
5600
Ω
(contact closed)
Secure
Infinite (broken wire, loop open)
Tamper
11200
Ω
(contact open)
Violated
Model
Model
Model
FAS-410x
FSA-410xLST
FSA-410xRST
FSA-410xT
FSA-410xR
FSA-410xLRST
FSA-410xS
FSA-410xRT
FSA-410xST
FSA-410xRS
For model numbers above: x=A (ULC) x=B (UL) x=C (CE)