background image

21

[005] - System Times
This  section  has  9  sub-sections,  1  for  each  of  the  8  parti-
tions, and 1 for the Bell timeout. This section programs the
entry and exit delays for the control panel. After entering sec-
tion  [005]  press  [01]  to  select  partition  1.  Enter  the  3-digit
delay  time  for  Delay  1  type  zones,  Delay  2  type  zones  fol-
lowed by the exit delay time.  Enter the next 2 digit sub-sec-
tion  number  to  program  the  next  partition.  Press  [#]  to  exit
the sub-menu and return to regular programming.
NOTE: 

Entry of 000 in these sections will result in a 255 sec-

ond time.

Sub-Sections 1-8 each require three 3-digit entries.
[01] - [08]   Entry Delay 1, Entry Delay 2, and Exit Delay per
Partition.

• Entry Delay 1: (001-255) Seconds

This value determines the Entry delay time for Delay 1 type
zones. The default Entry Delay 1 time is 30 seconds.

• Entry Delay 2: (001-255) Seconds

This value determines the Entry delay time for Delay 2 type
zones. The default Entry Delay 2 time is 45 seconds.

• Exit Delay: (001-255) Seconds

This value determines the Exit delay time when arming the
system. The default Exit Delay time is 120 seconds.
NOTE: 

For  SIA  FAR  Installations,  the  Exit  Delay  must  be

within the range of 045-255 seconds (Default 60 seconds). If
the Exit Delay is silent (Section 14, Option 6 or Stay Function
Key  Arming)  the  exit  delay must  be  twice the  programmed
value  but  must  not  exceed  255  seconds  (i.e.,  090-255  sec-
onds).

NOTE: 

For UL Installations, the Entry Delay plus the Commu-

nications Delay must not exceed 60 seconds.

NOTE: 

Exit Time Restart shall be disabled when the panel is

used in combination with T-Link TL250/TL300.

[09] Bell Cut-off: (001-255) Minutes
The Bell Cut-off for all 8 partitions is one entry.
The  siren  will  silence  after  the  number  of  minutes  pro-
grammed for the Bell Cut-off time have passed. The default
Bell Cut-off is 4 minutes
The panel supervises the Bell output. If an open condition is
detected, the panel will immediately indicate a trouble condi-
tion by beeping the keypad twice every 10 seconds to alert
the owner of the problem. The panel can send a Bell Circuit
Trouble  
and  Trouble  Restoral  reporting  codes  to  indicate
the  situation  (

See  Section  5.6  Communicator  Program-

ming

).

If the Temporal Three Fire Signal option is enabled, all Fire
signals will follow the Temporal Three Pattern as described
in NFPA 72. If turned OFF all Fire signals will sound a one
second on, one second off cadence.
If  Fire  Bell  Continuous  is  enabled,  the  alarm  output  will
sound  until  a  code  is  entered.  If  disabled,  the  alarm  will
sound  until  a  code  is  entered  or  the  bell  cut-off  time  has
expired.
NOTE: 

Only  fire  zones  will  follow  the  Temporal  Three  Fire

Signal.

Bell Cut-off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Section [005]
Bell Circuit Trouble Reporting Code . . . . . . . . . . . . . . Section [349]
Bell Circuit Trouble Restoral Reporting Code  . . . . . . . Section [350]
Temporal Three Fire Signal 
Enable/Disable . . . . . . . . . . . . . . . . . . . . .  Section [013], Option [8]
Fire Bell Continuous. . . . . . . . . . . . . . . . .  Section [014], Option [8]

[006] - Installer’s Code
The installers code is used to enter installers programming.
Enter  installers  programming  by  entering  [*][8][installers
code].  By  default  the  installers  code  is  5555  when  using  4
digit  access  codes  and  555555  when  using  6  digit  access
codes.

I[007] - Master Code
The Master code can only be changed by the Master or the
Installer  Code  if  it  has  been  programmed  to  change,  see
section [015] (6).

NOTE: 

For  EN  installations  the  installer  will  not  have

access  to Master  Code Programming. In order to return  the
master code to the factory default setting enter the Special
Installer  Function    [989][Installer's  Code][989]  (Master  Code
Factory Default Programming). This will allow the installer to
default the Master Code.

[008] - Maintenance Code/Guard Code
When used as Maintenance Code  it is a  Arm/Disarm code
only.    It  can  not  be  used  to  bypass,  activate  [*][7]  outputs,
program  other  user  codes  or  enter  the  [*][6]  menu.    It  can
access  and  arm  through  the  ESCORT5580.  Openings  or
Closings using this code report as a Special Opening/Clos-
ing and will log to the event buffer as “Maintenance Code”.
The Guard Code can arm the panel at any time.  However,
the Guard code can only disarm the system after an alarm,
tamper,  fault  or trouble condition  has  occurred.    It can  also
be  used  to  bypass  zones  and  activate  Command  Outputs.
Arming and Disarming by the Guard Code will log as “Clos-
ing (Opening) by Maintenance Code”. If a Command Output
that  requires  a  code  is  activated  with  the  Guard  Code,  no
User Log will be made. When zones are bypassed with the
Guard Code, the panel will log “[*][1] Access by User”..

[009]-[011] - Programmable Output Options 
Programmable  Outputs  are  programmed  with  a  two  digit
code indicated in the table below. Programmable outputs are
available on the following devices:

• PGM1  and  PGM2  on  the  PC1616/PC1832/PC1864

main board

• PGM3 and PGM4 on the PC1864 main board
• 8 low current outputs available with the PC5208 Output

Module

• 4 high current outputs available with the PC5204 Power

Supply/Output Module

• Section  [009]  is  used  to  program  two  PGM  outputs  on

the PC1616/PC1832/PC1864. 

• The  first  two  entries  of  Section  [010]  are  used  to  pro-

gram the last two outputs on the PC1832/PC1864, and
the first two on the PC5208.

• Section  [010]  is  used  to  program  the  PGM  outputs  on

the PC5208. 

• Section  [011]  is  used  to  program  the  PGM  outputs  on

the PC5204 and PGM3 and PGM4 on the PC1864.

Programming any of the outputs is a three step process: 
1. Select an option from the list below for the PGM output. 
2. Select the output attributes for the PGM output. 
3. Select the partitions on which the PGM output will operate.
The  following  is  a  list  of  the  programmable  output  options
and attributes.

PGM Attribute Programming  . . . . . . . . . . . . . . Section [501]-[564]

EN

Summary of Contents for PC1616

Page 1: ...gher PC1616 PC1832 PC1864 This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer The entire manual sh...

Page 2: ...bus Terminals RED BLK YEL GRN 6 Programmable Outputs PGM1 to PGM4 6 Zone Input Terminals Z1 to Z8 6 Telephone Connection Terminals TIP RING T 1 R 1 6 2 3 Wire Routing for Power Non Power Limited 6 2 4...

Page 3: ...one Assignments 35 Partitions and Zone Assignment 35 5 5 Communicator Programming 35 Communicator Telephone Numbers 35 301 First Telephone Number 35 302 Second Telephone Number 35 303 Third Telephone...

Page 4: ...toring 51 6 1 Partitions and Fire System Configuration 51 Fire Configuration 1 51 Fire Configuration 2 51 6 2 Fire Zones 51 Standard Fire Operation 51 Auto Verify Fire 51 Four Wire Smoke Detector Zone...

Page 5: ...your programming Be sure to record all your system programming in the Programming Worksheets If adding modules to your PowerSeries Control Panel refer to the Installation Instructions that come with...

Page 6: ...upervision for loss of primary power source AC Fail battery fail or battery low voltage Battery Trouble with indication provided on the keypad Internal clock locked to AC power frequency Operating Env...

Page 7: ...etails NOTE Only the first 32 zones on the PC1616 PC1832 PC1864 system can be used as wireless zones NOTE PC1616 expandable to 16 zones only PC5200 Power Supply Output Module The PC5200 can provide up...

Page 8: ...with removable door UL ULC Household Fire ULC Commercial Burglary Made with 22Ga steel Approximate Dimensions 287mm x 297mm x 76mm 11 3 x 11 7 x 3 0 PC5003C Hinged Door Description Main Control Cabine...

Page 9: ...ete description of how to pro gram the panel Section 5 0 contains complete descriptions of the various programmable features what options are available and how the options function The Programming Wor...

Page 10: ...inimum 6 4mm separation must be maintained at all points between power limited and non power limited wiring and connections NOTE Wire entry for power limited wiring must be sepa rated by a different e...

Page 11: ...t enter 0 for Global operation or enter 1 8 for Partitions 1 8 2nd digit enter 1 to 8 for Slot Assignment 5 Press the key twice to exit programming 6 Continue this procedure at each keypad until all h...

Page 12: ...matically search for all modules connected to the system for the next 60 seconds Do not perform any other oper ations during this 60 second period 6 Once the search is complete enter section 903 to co...

Page 13: ...ions for DEOL End of Line Resistors Section 013 Option 1 Double End of Line Resistors Section 013 Option 2 Fire Zone Wiring 4 wire Smoke Detectors All zones defined as Fire see section 5 2 Basic Progr...

Page 14: ...ngle End of Line and Double End of Line To connect the PGM output on a PK55XX RFK55XX key pad run one wire to the Z P terminal and the other to R PK55XX RFK55XX NOTE End of line resistors must be plac...

Page 15: ...ter the corresponding HEX digit 1 A 2 B 3 C 4 D 5 E 6 F After the correct HEX digit is entered the Ready light will continue to flash If another HEX digit is required press the corresponding number If...

Page 16: ...hrough the entry exit door the panel will bypass all Stay Away type zones The panel is now Stay armed The Bypass light will remain on to inform the home owner that the interior protection is bypassed...

Page 17: ...d The keypad will display Zone Search Zone Name 3 Enter the two digit number of the zone s to be bypassed 01 64 You can also use the keys to find the zone to be bypassed and then press to select the z...

Page 18: ...C5400 Printer module has a fault and is off line or T Link Troubles Users can view specific conditions in the Event Buffer Light 4 General System Tamper Tamper has been detected from a module Light 5...

Page 19: ...rtition number 1 8 to toggle it on or off NOTE Partition programming is NOT supported by the fol lowing keypads PC5508 Z PC5516 Z PC5532 Z versions v2 00 and lower LCD5500 Z version 2 x and lower LCD5...

Page 20: ...tempt to call the downloading computer NOTE The downloading computer must be waiting for the panel to call before downloading can be performed 7 For Future Use 8 User Walk Test 6 User Functions allows...

Page 21: ...xit delay The Quick Arm feature must be enabled for this key to function Section 015 Option 4 If Quick Arming is not enabled the user must enter their access code after pressing the function key in or...

Page 22: ...selected the Trouble light will turn on if a trouble con dition is present and the Armed light will turn on if all the partitions are armed To select a partition the user must press and hold one of k...

Page 23: ...and transmission by the communicator is delayed by 30 seconds If the alarm is acknowledged by pressing any key within 30 seconds the bells will silence and the transmission will be aborted If the ala...

Page 24: ...armed in the Away Mode This zone type is useful for motion detectors in an installation that must not follow the Entry Delay after a Delay zone is violated but must still retain the Stay Away function...

Page 25: ...ing Code Section 349 Bell Circuit Trouble Restoral Reporting Code Section 350 Temporal Three Fire Signal Enable Disable Section 013 Option 8 Fire Bell Continuous Section 014 Option 8 006 Installer s C...

Page 26: ...e exit delay begins 07 Keypad Buzzer Follow This output will activate switch to ground when any of the following events occur and will remain active for as long as the keypad buzzer is active Door Chi...

Page 27: ...PGM type will activate 22 Command Output 4 This output is activated by entering the 7 4 command The configuration of the corresponding attributes deter mines how this PGM type will activate 23 Silent...

Page 28: ...ication of alarms and the initiation of the confirmation time the toggle option TX Delay During Entry Only must be enabled The transmission delay attribute must also be enabled for all zones and the c...

Page 29: ...emory the bell will emit a series of three squawk pairs to indicate the alarm memory NOTE If you enable the Bell Squawk on Arming Disarming the bell will sound arm disarm bell squawks for all access c...

Page 30: ...call direc tion options Fire Auxiliary and Panic key NOTE The Fire Auxiliary Panic keys will operate even if Keypad Blanking and Keypad Lockout are active See Section 5 3 Basic Programming PWS Sect 3...

Page 31: ...ave Mode ON Power Save Mode Enabled If AC power fails all keypad lights including backlighting will be shut OFF The keypad lights will come back ON after a keypress Entry delay Audible Alarm or keypad...

Page 32: ...the Auto arm and Test Transmissions programming OFF Daylight Savings Time Disabled The panel will make no automatic time adjustments for Daylight Sav ings time 7 For Future Use 8 Bell Squawk on Away A...

Page 33: ...larm when faulted while stay armed Zone types 9 24 Hour Supervisory 12 24 Hour Hold Up 26 24 Hour Non Alarm do not generate an audible alarm in any armed state stay or away OFF Wireless Zone Fault Doe...

Page 34: ...try Procedure The following zone type alarms will follow bell delay if a zone violation occurs while entry delay is active on the partition Instant Interior Interior Stay Away Delay Stay Away 24 Hr Su...

Page 35: ...not be locked out after an alarm occurs 5 Engineer s Reset ON Engineer s Reset Enabled If the panel has gone into alarm during the previous armed period or if a 24 Hour alarm has occurred armed or dis...

Page 36: ...ate tamper alarms The panel will generate a silent trouble NO trouble beeps but the Trouble LED is turned ON called RF Device Delinquency that s only viewable in 2 Trouble Mem ory The user can overrid...

Page 37: ...e system trouble beeps will not be sounded at the keypad OFF Trouble Beeps will Sound Every 10 Seconds When a trouble is detected on the system trouble beeps will be sounded at the keypad NOTE This op...

Page 38: ...ll not log or transmit If a second zone is violated within the Cross Zone Timer s seconds duration the panel will go into the appropriate alarm sequence and will communicate both zone alarms No Police...

Page 39: ...233 Partition 5 Zone Assignments Sections 234 to 241 Partition 6 Zone Assignments Sections 242 to 249 Partition 7 Zone Assignments Sections 250 to 257 Partition 8 Zone Assignments Sections 258 to 265...

Page 40: ...ral Reporting Codes Zones 1 to 64 If the Restoral on Bell Timeout option is selected the panel will send the Zone Restoral Reporting Code for the zone when the alarm output times out AND the zone is s...

Page 41: ...o Arm Cancellation This reporting code is transmitted when the Auto Arming sequence is canceled or Postponed Special Opening A Special Opening Reporting Code will be transmitted if the Partition s is...

Page 42: ...eporting Code in place of the standard Peri odic Test Transmission if any of the following conditions exist Fire Zone Trouble Zones 1 64 Battery Trouble PC1616 PC1832 PC1864 PC520X Fire Zone Alarm Zon...

Page 43: ...med as 00 the panel would not report If the SIA Sends Automatic Reporting Codes option is dis abled the panel will operate as follows 1 If the reporting code for an event is programmed as 00 or FF the...

Page 44: ...mple If you program the zone 3 alarm reporting code as 31 the panel will send event code 1 in channel 3 The panel will send the number 5 for each of the other channels so that the event code will look...

Page 45: ...tores This value defines the number of attempts alarm and restore pairs per zone that the panel will log and communicate before it shuts down for that zone swinger shutdown Valid entries are 000 to 01...

Page 46: ...his interval is in minutes or days is determined on Section 702 Option 3 NOTE If using Test Transmission Exception a value of 001 will disable the Test Transmission Exception feature Wireless Zone Low...

Page 47: ...y armed Activity on Bypassed zones does not affect this timer The timer is reset on arming OFF Delinquency Follows Arming Closing Delinquency This reporting code is sent whenever the programmed number...

Page 48: ...2 Walk Test Communication ON Zone Alarms Communicate during Walk Test Enabled Zone alarms that occur during Walk Test will communicate if programmed to do so OFF Zone Alarms Communicate during Walk T...

Page 49: ...will be busy for the duration of the PC Link connection The status LEDs will display the current system status on the keypad where the PC Link was initiated For more information on connect ing the PC...

Page 50: ...sheets for the PGM output types defaults CAUTION Select the normal and active states of each PGM output to ensure that undesirable output states do not occur after a loss and restore of AC power If yo...

Page 51: ...Trouble 8 Loss of Clock Loss of Time Trouble PGM Output Types 10 System Event 1 Burglary Delay Instant Interior Stay Away and 24 Hour Burg Zone Types 2 Fire F Key Fire Zone 3 Panic P Key and Panic zon...

Page 52: ...l access codes on the system will be 4 digits in length For any existing codes the last 2 digits are removed 6 Busy Tone ON Busy Tone Detection Enabled If these tones are detected the communicator wil...

Page 53: ...n 901 Zones do not have to be restored to stop the test After the test is complete check the Event Buffer to ensure that the Audible Silent 24 hr PGM alarms have been restored NOTE The Alarm Memory is...

Page 54: ...section 991 again 993 999 Factory Defaults On occasion it may be necessary to default the main control panel or one of the modules that can be connected There are several different defaults available...

Page 55: ...stor this will be indicated as a Zone Trouble Ground Fault resistance 40k to earth ground indicated as a Ground Fault Trouble on PC5700 zone 7 Typical Fire Devices used on this zone type are Heat Dete...

Page 56: ...entering 7 2 in order to reset smoke detectors Subsequent Alarm Operation If the alarm notification appliances have been silenced manually or automatically and a subsequent fire alarm is initiated the...

Page 57: ...ire Keys on any keypad are pressed for two seconds NOTE For commercial applications do not program the F key for keypads that are readily accessible by the public For more information regarding this k...

Page 58: ...pro grammed as not bypassable Casual Users The installer should caution the user s not to give system information to casual users e g codes bypass methods etc to baby sitters or service people Only th...

Page 59: ...Cancel Annunciation 328 8th entry Access to the reporting code for Alarm Cancelled Annunciate that a Cancel was transmitted Default Enabled Required Duress Feature 5 Master Code 33rd and 34th entries...

Page 60: ...ed A R 4 A6 BC 00 329 F Key Alarm Rest Keypad fire alarm alarm and restore rep codes sent together A R 1 15 FA 00 FH 00 329 A Key Alarm Rest Keypad auxiliary alarm alarm and restore rep codes sent tog...

Page 61: ...e TLM Trouble Restore occurs on the PC5700 MA R 3 52 LR XX A R alarms restorals T R tampers restorals O C openings closings MA R miscellaneous alarms restorals T test transmissions UU user number user...

Page 62: ...e power from the control panel must be UL Listed for the intended application and operate over the range of 11 6 12 6VDC residential 12 0VDC commercial The DSC Bravo Series are recommended UL Listed m...

Page 63: ...rsons b The connection to the mains supply must be made as per the local authorities rules and regulations An appropriate disconnect device must be provided as part of the building installation Where...

Page 64: ...tion WARNING High Voltage Disconnect AC Power and telephone lines before servicing WARNING 220 240V 50 60Hz 200mA AC PC5003C Cabinet Shown Use Model Power UC1 for 2 Battery Installations CON1 BAT BAT...

Page 65: ...ual NOTE Do not combine the 2 wire smoke detector and 4 wire smoke detector on PGM2 only 2 wire smoke detectors on PGM2 SMOKE DETECTOR POWER 12 VDC IN OUT NO ALM OUT IN BLK WHT RED GRN LATCHING 4 WIRE...

Page 66: ...International Programming 47 K Key 26 Key Annunciation 26 Keybus Fault 29 Keypad Assignment 7 Keypad Blanking 27 Keypad Buzzer Follow 22 Keypad Commands 12 Keypad Lockout 24 Keypad Lockout Options 24...

Page 67: ...It is important that a security system be reviewed periodically to ensure that its features remain effective and that it be updated or replaced if it is found that it does not pro vide the protection...

Page 68: ...ill notify you in advance that temporary discontinuance of service may be required But if advance notice is not practical the Telephone Company will notify the customer as soon as possible Also you wi...

Reviews: