21
[005] - System Times
This section has 9 sub-sections, 1 for each of the 8 parti-
tions, and 1 for the Bell timeout. This section programs the
entry and exit delays for the control panel. After entering sec-
tion [005] press [01] to select partition 1. Enter the 3-digit
delay time for Delay 1 type zones, Delay 2 type zones fol-
lowed by the exit delay time. Enter the next 2 digit sub-sec-
tion number to program the next partition. Press [#] to exit
the sub-menu and return to regular programming.
NOTE:
Entry of 000 in these sections will result in a 255 sec-
ond time.
Sub-Sections 1-8 each require three 3-digit entries.
[01] - [08] Entry Delay 1, Entry Delay 2, and Exit Delay per
Partition.
• Entry Delay 1: (001-255) Seconds
This value determines the Entry delay time for Delay 1 type
zones. The default Entry Delay 1 time is 30 seconds.
• Entry Delay 2: (001-255) Seconds
This value determines the Entry delay time for Delay 2 type
zones. The default Entry Delay 2 time is 45 seconds.
• Exit Delay: (001-255) Seconds
This value determines the Exit delay time when arming the
system. The default Exit Delay time is 120 seconds.
NOTE:
For SIA FAR Installations, the Exit Delay must be
within the range of 045-255 seconds (Default 60 seconds). If
the Exit Delay is silent (Section 14, Option 6 or Stay Function
Key Arming) the exit delay must be twice the programmed
value but must not exceed 255 seconds (i.e., 090-255 sec-
onds).
NOTE:
For UL Installations, the Entry Delay plus the Commu-
nications Delay must not exceed 60 seconds.
NOTE:
Exit Time Restart shall be disabled when the panel is
used in combination with T-Link TL250/TL300.
[09] Bell Cut-off: (001-255) Minutes
The Bell Cut-off for all 8 partitions is one entry.
The siren will silence after the number of minutes pro-
grammed for the Bell Cut-off time have passed. The default
Bell Cut-off is 4 minutes
The panel supervises the Bell output. If an open condition is
detected, the panel will immediately indicate a trouble condi-
tion by beeping the keypad twice every 10 seconds to alert
the owner of the problem. The panel can send a Bell Circuit
Trouble and Trouble Restoral reporting codes to indicate
the situation (
See Section 5.6 Communicator Program-
ming
).
If the Temporal Three Fire Signal option is enabled, all Fire
signals will follow the Temporal Three Pattern as described
in NFPA 72. If turned OFF all Fire signals will sound a one
second on, one second off cadence.
If Fire Bell Continuous is enabled, the alarm output will
sound until a code is entered. If disabled, the alarm will
sound until a code is entered or the bell cut-off time has
expired.
NOTE:
Only fire zones will follow the Temporal Three Fire
Signal.
Bell Cut-off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Section [005]
Bell Circuit Trouble Reporting Code . . . . . . . . . . . . . . Section [349]
Bell Circuit Trouble Restoral Reporting Code . . . . . . . Section [350]
Temporal Three Fire Signal
Enable/Disable . . . . . . . . . . . . . . . . . . . . . Section [013], Option [8]
Fire Bell Continuous. . . . . . . . . . . . . . . . . Section [014], Option [8]
[006] - Installer’s Code
The installers code is used to enter installers programming.
Enter installers programming by entering [*][8][installers
code]. By default the installers code is 5555 when using 4
digit access codes and 555555 when using 6 digit access
codes.
I[007] - Master Code
The Master code can only be changed by the Master or the
Installer Code if it has been programmed to change, see
section [015] (6).
NOTE:
For EN installations the installer will not have
access to Master Code Programming. In order to return the
master code to the factory default setting enter the Special
Installer Function [989][Installer's Code][989] (Master Code
Factory Default Programming). This will allow the installer to
default the Master Code.
[008] - Maintenance Code/Guard Code
When used as Maintenance Code it is a Arm/Disarm code
only. It can not be used to bypass, activate [*][7] outputs,
program other user codes or enter the [*][6] menu. It can
access and arm through the ESCORT5580. Openings or
Closings using this code report as a Special Opening/Clos-
ing and will log to the event buffer as “Maintenance Code”.
The Guard Code can arm the panel at any time. However,
the Guard code can only disarm the system after an alarm,
tamper, fault or trouble condition has occurred. It can also
be used to bypass zones and activate Command Outputs.
Arming and Disarming by the Guard Code will log as “Clos-
ing (Opening) by Maintenance Code”. If a Command Output
that requires a code is activated with the Guard Code, no
User Log will be made. When zones are bypassed with the
Guard Code, the panel will log “[*][1] Access by User”..
[009]-[011] - Programmable Output Options
Programmable Outputs are programmed with a two digit
code indicated in the table below. Programmable outputs are
available on the following devices:
• PGM1 and PGM2 on the PC1616/PC1832/PC1864
main board
• PGM3 and PGM4 on the PC1864 main board
• 8 low current outputs available with the PC5208 Output
Module
• 4 high current outputs available with the PC5204 Power
Supply/Output Module
• Section [009] is used to program two PGM outputs on
the PC1616/PC1832/PC1864.
• The first two entries of Section [010] are used to pro-
gram the last two outputs on the PC1832/PC1864, and
the first two on the PC5208.
• Section [010] is used to program the PGM outputs on
the PC5208.
• Section [011] is used to program the PGM outputs on
the PC5204 and PGM3 and PGM4 on the PC1864.
Programming any of the outputs is a three step process:
1. Select an option from the list below for the PGM output.
2. Select the output attributes for the PGM output.
3. Select the partitions on which the PGM output will operate.
The following is a list of the programmable output options
and attributes.
PGM Attribute Programming . . . . . . . . . . . . . . Section [501]-[564]
EN