26
[015] - Third System Option Codes
6
Audible Exit Beeps
ON
Audible Exit With Urgency
The keypad will sound a pulsing tone (once per second) during the Exit Delay.
For the last 10 seconds of the Exit Delay, the keypad and bell / siren (if enabled) will sound a different tone
(3 tones per second) to warn that the Exit Delay is about to expire.
NOTE: Users can restart the exit delay while it is counting down by pressing the Away key. The
system will not log the user who re-started the exit delay, unless the Quick Arming Disabled/
Function Keys Require Code option is turned on (section [015], option [4]).
NOTE: If the system has been Stay armed, or armed with no entry delay ([*][9]), pressing the
Away key will not re-start the exit delay.
OFF
Silent Exit Delay
The keypad will not sound during the Exit Delay.
7
Exit Delay Termina-
tion
ON
Exit Delay Termination Enabled
The Exit Delay will be terminated once a Delay 1 Zone for the entry/exit
door or area is restored. All audible options associated with the exit delay will be silenced when the Exit
Delay is terminated. Force-Armable Delay 1 type zones will also terminate the exit delay.
NOTE: If a Delay type zone is violated then secured during the exit delay, the exit delay will be
terminated and the panel will be armed immediately.
OFF
Exit Delay Termination Disabled
The Exit Delay timer will continue to count even after the Delay Zone
for the entry/exit door or area is restored. All audible options associated with the Exit Delay will function
until the time programmed for the Exit Delay has elapsed.
8
Fire Bell Timeout
ON
Fire Bell is Continuous
The Bell output will sound for all Fire type alarms until an access code is entered to
silence the alarm or disarm the system regardless of the time programmed for Bell Timeout in Section
[005].
OFF
Fire Bell Follows Timeout
The Bell output will sound for all Fire type alarms for the duration of Bell time-
out or until an access code is entered.
Option
Definition
On/Off
Description
1
[F] Key Annunciation
ON
[F] Key Enabled
Pressing and holding the [F] key for 2 seconds will generate a Fire alarm. The keypad will
sound a set of 3 beeps to acknowledge the valid alarm and the bell or siren will pulse one second on, one
second off if option 8 of Section [013] is disabled (Standard Fire option). If Fire Bell is Continuous (Section
[014], Option 8) is selected the alarm output will sound until a code is entered, otherwise it will sound until
a code is entered or the alarm output times out. Communication of the signal to central station is immedi-
ate. The bell will sound for the length of Bell time-out. An alarm reporting code (if programmed) will be
transmitted.
NOTE: If enabled, this key will generate alarms at all times except while in a valid installer pro-
gramming section on an LED keypad. The [F] key is used for scrolling through data on LED key-
pads in the installer programming sections.
NOTE: Fire, Auxiliary, and Panic key transmissions follow the partition 1 alarm/restore call direc-
tion options (Fire, Auxiliary, and Panic key)
NOTE: The Fire, Auxiliary, Panic keys will operate even if Keypad Blanking and Keypad Lockout
are active (See Section 5.3 Basic Programming PWS Sect 3 [012]).
OFF
[F] Key Disabled
The [F] key will not sound or report an alarm when pressed.
2
[P] Key Annunciation
ON
[P] Key Audible
When a valid [P] key alarm is generated, the Keypad buzzer will sound a series of 3 beeps
to acknowledge the alarm. The bell or siren will also sound for the length of Bell timeout.
NOTE: Fire, Auxiliary, and Panic key transmissions follow the partition 1 alarm/restore call direc-
tion options (Fire, Auxiliary, and Panic key)
NOTE: The Fire, Auxiliary, Panic keys will operate even if Keypad Blanking and Keypad Lockout
are active (See Section 5.3 Basic Programming PWS Sect 3 [012]).
OFF
[P] Key Silent
When a valid [P] key alarm is generated: the Keypad buzzer and the bell output will remain
silent, the alarm transmission will still be transmitted if programmed.
3
Quick Exit
ON
Quick Exit Enabled
When the system is armed, users may enter the [*][0] Command to allow a single
Delay 1 or Delay 2 Zone to be activated so they may leave the premises. Only one Delay zone may be acti-
vated. Additional activity on another Delay zone will initiate its respective alarm sequence. If the Delay zone
is still open two minutes after the [*][0] command is entered, the Entry Delay will be initiated. If armed in
the Stay mode, the automatic bypass on Stay/Away zones will not be removed.
OFF
Quick Exit Disabled
When the system is armed, users can not perform a quick exit pr pressing [*][0].
4
Quick Arming/Func-
tion Key
ON
Quick Arming Enabled/Function Keys Do Not Require Code
[*][0] arming and Stay/Away Function
Keys may be used to arm the system without the entry of a valid access code. All other function Keys may
also be used without the entry of an access code.
OFF
Quick Arming Disabled/Function Keys Require Code
[*][0] arming is not permitted, and all Function
Keys require the entry of an access code to activate (including Stay/Away keys).
NOTE: This option must be on if less than version 3.0 of the PC5132 is used.
5
Bypass Access Code
ON
Access Code Required to Bypass Zones
After entering the [*][1] Bypass Zones Command, an access
code must be entered before zones may be bypassed.
OFF
Access Code Not Required to Bypass Zones
Enter [*][1] Bypass Zones Command to bypass zones.
6
Master Code
ON
Master Code Not User Changeable
The Master Code (Access Code 40) may not be changed by the user,
and may only be programmed in the Installer’s Programming Mode.
OFF
Master Code User-Changeable
The Master Code may be programmed by the user using the [*][5][Mas-
ter Code] command. The Master Code may also be programmed in the Installer’s Programming Mode.
7
Telephone Line Mon-
itor
ON
Telephone Line Monitor enabled
The TLM function will be active and the system will indicate a Trouble
#3 condition when using the [*][2] View Trouble Conditions Command.
NOTE: For IMQ-Security certified installations the TLM option shall be enabled.
OFF
Telephone Line Monitor disabled
The TLM function will be shut off and telephone line troubles will not
be indicated by the system.
Option
Definition
On/Off
Description