Page 46 of 87
DGH 55B-INS-OMENG Rev: 3
Configuration Menu Parameters
Press the CFG key:
Enter the Configuration Menu
Press the ENT key repeatedly:
Navigate down the Parameters List
Press the CFG key again:
Exit the Configuration Menu
Parameter
Availability
Parameter
[default value]
Changing A
Setting
Range
Result/Description
Only available if in
Mapping Mode
Disp Bias Meas
[Enabled]
Press ↑ or ↓ key to
enable or disable
Disabled
The device WILL NOT display measurement bias
while in Mapping Mode
Enabled
The device WILL display measurement bias while
in Mapping Mode
Only available if in
Mapping Mode and
Disp Bias is enabled
Amount Of Bias
[100%]
Press ↑ or ↓ key to
change the value
1% to 199%
Selects the percentage to calculate biased
measurements
Only available if in
Mapping Mode
Good Meas Delay
[1.0 sec]
Press ↑ or ↓ key to
change the value
1.0 to 9.5
Period of time (in seconds) after a measurement
that the device will display the result before
advancing to the next measurement position
Only available if in
Mapping Mode
Poor Appl Delay
[2.0 sec]
Press ↑ or ↓ key to
change the value
1.0 to 9.5
Period of time (in seconds) after a poor
applanation occurs before the unit will
automatically advance to the next measurement
position
Always Available
Delay to Standby
[1.0 min]
Press ↑ or ↓ key to
change the value
0.5 to 9.5
Period of time (in minutes) that the device will
wait before automatically switching to Standby
Mode
Always Available
Battery Type
[Rechargeable]
Press ↑ or ↓ key to
change the value
Alkaline
The device is set to monitor voltages for alkaline
batteries.
Rechargeable
The device is set to monitor voltages for
rechargeable batteries.
Always Available
Contrast
[7 segments]
Press ↑ or ↓ key to
change the value
1 to 14
(segments)
Adjusts display contrast for desired viewing.
Always Available
Volume
[7 segments]
Press ↑ or ↓ key to
change the value
1 to 14
(segments)
Adjusts alarm volume to desired level.
Always Available
Date / Time
Press OS to Format
Press OD to Set
Format
Use the ↑ or ↓ key to select either
MMM-DD-YYYY or DD-MMM-YYYY.
The device will display the date in this format.
Set
Use the OD or OS keys to move the cursor left or
right. Use the ↑ or ↓ key to change the values.
This will set the date and time for the device. Date
and time must be reset after batteries are changed.