![Desin Instruments HS-7000 Series General Instructions Manual Download Page 24](http://html1.mh-extra.com/html/desin-instruments/hs-7000-series/hs-7000-series_general-instructions-manual_2486942024.webp)
24
OPERATION OF FUNCTIONS OF MAIN MENU
CONTROL SETPOINTS [SP 1] [SP 2] and [SP 3]
Allow to see and modify the setpoint values of each loop.
Each one of the
SP 1...3
, could be linked en any of the used Loops L1, L2 or L3, or could be
protected under one of the 4 Password levels. Besides, could be visible, modifiable or hidden
(by program) in the menu, depending on the user requirements.
The maximum limit is ± 32000 points, however, by programming, could be limited to any value
in-between.
NOTE:
The
HS-7300,
although by communication a range of ± 32000 points could be set,
because the display available is a 4-digit display, --1999 to 9999, over these limits will show
the over range messages Over or Unde.
The number od decimals 0, 1, 2 o 3, can be defined by program or by front keypad. Refer to
Configuration.
CONTROL SETPOINT SETTING
VERY IMPORTANT:
There are two modes to modify the Setpoint value (SP).
●
Direct mode:
Increasing or decreasing the value using the keys
and
.
●
Shift mode:
Shifting digit by digit and increasing from 0 to 9.
Modification of Control Setpoints [SP 1] [SP 2] and [SP 3]
- Select using key
the loop to check
L1 , L2 or L3
, indicated by the corresponding LED.
Each loop
L1 , L2 or L3
shows the setpoint
[SP 1]
,
[SP 2]
or
[SP 3]
respectively
.
DIRECT ACCESS PROCEDURE:
- Once the loop to modify is selected, press the key
and the display
SP
start flickering,
(the middle display in the
HS-7300
or the lower one in the
HS-7200
when programmed as
controller).
- Modify the setpoint using the keys
or
until the desired value.
- Press the key
the display stop flickering and return to its inicial status.
This method can be used to realize small modifications of the
SP
value.
SHIFT MODE PROCEDURE:
- Once the loop to modify is selected, press the key
twice, the display will show
SP 1
(in
loop 1) or
SP 2
or
SP 3
(in loops 2 and 3 respectively). The unity digit (first to the right)start
flickering.
- Press to modify the value of the flickering didgit, then press
to shift to the second digit,
and repat the process using key
until the desired value is achieved in each digit.
- Once the value is modified, press
to store the new value and
to go to the next option,
or several times until
NORMAL DISPLAY
is reached
.
NOTE:
If the introduced value of any of the Setpoints
SP 1
,
SP 2
or
SP 3
, is higher than the
High or Low limits already set in the Configuration menu, this value will be displayed but when
validation key
is pressed, the value stored will be the High or Low preset value, depending
on the exceeded limit.