29
interface)
This signal indicates the status of input 4 at the hardware
interface.
(see
SysStatus INT
System status
This parameter indicates the system status of the AST40 –
screwdriving controller.
(for possible status values, see
ErrorCode WORD
Error Code
This parameter indicates the internal errors in the module.
(for possible errors, see below)
Table 12:
Data structure of the status signals (UDT22)
7.6.1.3.4 Description of the – Error Code:
Error
Description
FF00
Error in the input address range
Cause:
The transfer parameter
I_AddrX (X=1-4)
is not assigned or there is a value of smaller
or equal to 0.
FF01
Error while reading the input module 1 (I_Addr1)
Possible causes:
An incorrect input module has been entered in the hardware configuration. Input
module 1 must be configured with "64 bytes in".
Incorrect start address of the input module 1 at the interface parameter I_Addr1
FF02
Error while reading the input module 2 (I_Addr2)
Possible causes:
An incorrect input module has been entered in the hardware configuration. Input
module 2 must be configured with "64 bytes in".
Incorrect start address of the input module 2 at the interface parameter I_Addr2
FF03
Error while reading the input module 3 (I_Addr3)
Possible causes:
An incorrect input module has been entered in the hardware configuration. Input
module 3 must be configured with "64 bytes in".
Incorrect start address of the input module 3 at the interface parameter I_Addr3
FF04
Error while reading the input module 4 (I_Addr4)
Possible causes:
An incorrect input module has been entered in the hardware configuration. Input
module 4 must be configured with "32 bytes in".
Incorrect start address of the input module 4 at the interface parameter I_Addr4
FF10
Error in the output address range
Cause:
The transfer parameter
I_AddrX (X=1-4)
is not assigned or there is a value of smaller
or equal to 0.
FF11
Error while writing to the output module 1 (O_Addr1)
Possible causes:
An incorrect output module has been entered in the hardware configuration.
Output module 1 must be configured with "64 bytes out".
Incorrect start address of the output module 1 at the interface parameter
O_Addr1
FF12
Error while writing to the output module 2 (O_Addr2)
Possible causes: