- 86 -
RMS Current and Frequency Measurements Menu
RMS Current Measurements Menu measures
amplitudes of current waves of frequencies from 50 Hz
/ 60 Hz (1st order harmonic) to 500 Hz / 600 Hz (10th
order harmonic) to evaluate the root mean square
value of the line primary current and displays the
momentary and peak results. The menu contains:
• R, S, T line and N RMS current values, and
Momentary network frequency value.
The values displayed on the menu are the network
primary values.
As DEMA CPM 310 G evaluates the primary current
values by utilizing the information acquired from the
secondary signals and the
CT Settings
menu, the
values at the
CT Settings
menu must be set correctly to
make sure
RMS Current Measurements Menu
displays
correct evaluations.
RMS current values are measured and displayed within
the range of (0.1-40.0) I
n
and (0.1-40.0) I
en
. Values
lower than the base limit will neither be measured nor
be displayed, while values exceeding the upper limit
will be evaluated and displayed as 40 I
n
or 40 I
en
.
If the S1 (BIGDISP) button is pressed on the menu, the
ampermeter interface (shown at the bottom picture) is
displayed. This ampermeter shows all the current
values in the largest visual format possible, to make it
easier for the operator to observe the current readings.
Pressing any other button than the Reset button will
lead the screen to the
RMS Current Measurements
menu.
Below the I
r
, I
s
, I
t
and I
n
values, the momentary
frequency measurement is displayed. Note that this
measurement will not be able to be done if no current
can be measured from the CTs (e.g. when the circuit breaker is in open position) and the
f
value will
be displayed as “XX.XX”, as on the top picture.
WARNING!
To ensure the correct operation and measurements of DEMA CPM 310 G relays, the
Frequency
parameter at the
System Settings
Menu has to be set correctly! Inappropriate settings may cause in
protection faults and incorrect measurements!
The
Frequency
parameter in the
System Settings
Menu is set to 50 Hz by default. If the network
nominal power frequency is 50 Hz, no changes are needed to be done on the control; however, if the
network nominal power frequency is 60 Hz, the following address is to be followed to set the
parameter correctly to ensure safe and expected functionality of the unit:
Main Screen » Menu » System Settings » Frequency » 60 Hz
□
Main Screen » Menu »
Measurements » RMS Current
Digital Ampermetre
Summary of Contents for CPM 310 G
Page 1: ...CPM 310 G Digital Overcurrent Protection Relay User Application Manual vEN 2016 03...
Page 2: ...2...
Page 6: ...6 ABOUT DEMA...
Page 11: ...11 INTRODUCTION...
Page 32: ...32 PACKING LABELING INFORMATION...
Page 34: ...34 OPERATING MANUAL...
Page 53: ...53 RELAY MENUS MANUAL...
Page 55: ...55 The Menu Tree...
Page 56: ...56...
Page 57: ...57...
Page 58: ...58...
Page 59: ...59...
Page 60: ...60...
Page 61: ...61...
Page 128: ...128 DIGICONNECT PC PROGRAM MANUAL...
Page 189: ...189 APPLICATION DIAGRAMS...
Page 191: ...191 Sample Power Transformer Protection Application Diagram...
Page 193: ...193 FUNDAMENTAL CABLING DIAGRAM...
Page 203: ...203 APPLICATION DIAGRAM NO 10 RS485 Cabling...
Page 204: ...204 TECHNICAL DATA...
Page 220: ...220 GLOSSARY...