Trip Circuit Supervision
CPM 310 G relays are capable of checking the electrical continuity of the trip circuit (the circuit
that connects the
Trip Relay
(RL
TRIP
) of CPM 310 G and the release coil of the CB); by utilizing
the Trip Circuit Supervision function.
To utilize the function, the diagram below must be applied and an available programmable
input (e.g. I1 on the diagram below) must be programmed as “TripCirSup”.
If electrical discontinuity is detected after the commissioning of the function, the function
counts for the time determined by the tTCS before the Alarm LED is activated and
CB Alarm
and
TripCirSup
messages are displayed on the
Alarm Menu
. □
Trip Circuit Supervision Application Diagram