- 210 -
Technical Characteristics
Pick-up Current
For all threshold values: over 1.05 times the set value.
Current Reset Ratio (Hysteresis)
~%95
Instantaneous Trip Time
~35 ms
Drop-out Time
~40 ms
Trip Time Delays for Earth Thresholds
Tripping delay ranges for earth fault protection is the same with those for phase
fault protection. DMT and IDMT characteristics available.
Reset Time Delays for Earth Thresholds Reset delay ranges for earth fault protection is the same with those for phase fault
protection. DMT and IDMT characteristics available.
Measurement Technique
RMS current.
Threshold Setting Range
I
Θ
> = (0.1-3.2) I
n
, in steps of 0.01 I
n
.
Thermal Constant Setting Range
T
e
: (1-200) min, in steps of 1 min.
Thermal Trip Level Multiplier (k) Setting
Range
k : 1-1.5, in steps of 0.01.
Thermal Trip Level Setting Range
Trip Θ : %(50-200), in steps of: %1.
Thermal Alarm Level Setting Range
Alarm Θ : %(50-200), in steps of: %1.
Measurement Technique
%(I
2
/I
1
)> where I
1
is fundamental harmonics of positive sequence and I
2
is
fundamental harmonics of negative sequence current.
%(I
2
/I
1
)> Setting Range
%(20-100), in steps of %1.
Tripping Delay Setting Range
(1-14,400) s, in steps of 1 s.
Measurement Technique
Fundamental harmonic.
Threshold Setting Range
(0.1-40) I
n
There are 2 independent thresholds available for negative sequence overcurrent
protection function.
I
2
> = (0.1-40) I
n
, in steps of 0.01 I
n.
I
2
>> = (0.1-40) I
n
, in steps of 0.01 I
n.
Pick-up Current
~1.05 I
s
Current Reset Ratio (Hysteresis)
~%95
Tripping Delay Setting Range
The range is the same with phase overcurrent protections'.
Resetting Delay Setting Range
The range is the same with phase overcurrent protections'.
Measurement Technique
Fundamental harmonic.
Threshold Setting Range
I< = (0.02-1.0) I
n
, in steps of 0.01 I
n.
Tripping Delay Setting Range
tI< = (0.01-150) s, in steps of 0.01 s.
Triggering Condition
Current measurement below the set level while 52a input is active.
Current Reset Ratio (Hysteresis)
~ %105
Pick-up Current
~ I<
2.6 Undercurrent Protection (I<) [ANSI 37]
2.2 Earth Overcurrent Protection [ANSI 50N/51N] (Continued)
2.3 Thermal Overload Protection [ANSI 49]
2.4 Broken Conductor Detection [%(I2/I1)>]
2.5 Negative Sequence Overcurrent Protection (I2>) [ANSI 46]
Thresholds and Setting Ranges
Summary of Contents for CPM 310 G
Page 1: ...CPM 310 G Digital Overcurrent Protection Relay User Application Manual vEN 2016 03...
Page 2: ...2...
Page 6: ...6 ABOUT DEMA...
Page 11: ...11 INTRODUCTION...
Page 32: ...32 PACKING LABELING INFORMATION...
Page 34: ...34 OPERATING MANUAL...
Page 53: ...53 RELAY MENUS MANUAL...
Page 55: ...55 The Menu Tree...
Page 56: ...56...
Page 57: ...57...
Page 58: ...58...
Page 59: ...59...
Page 60: ...60...
Page 61: ...61...
Page 128: ...128 DIGICONNECT PC PROGRAM MANUAL...
Page 189: ...189 APPLICATION DIAGRAMS...
Page 191: ...191 Sample Power Transformer Protection Application Diagram...
Page 193: ...193 FUNDAMENTAL CABLING DIAGRAM...
Page 203: ...203 APPLICATION DIAGRAM NO 10 RS485 Cabling...
Page 204: ...204 TECHNICAL DATA...
Page 220: ...220 GLOSSARY...