- 209 -
Technical Characteristics
Measurement Technique
Fundamental harmonic.
Current Measurement Range
(0.1-40) I
n
Important Note: It must be kept in mind that CPM 310 measures currents up to 40
In, and no precise evaluations can be done for current values higher than this.
Current Threshold Setting Range
3 independent thresholds, set as multipliers of In.
1.threshold and set interval : (0.1-25) I
n
, in 0.01 I
n
steps.
2.threshold and set interval : (0.5-40) I
n
, in 0.01 I
n
steps.
3.threshold and set interval : (0.5-40) I
n
, in 0.01 I
n
steps.
Pick-up Current
For all threshold values: over 1.05 times the set value.
Current Reset Ratio (Hysteresis)
~%95
Instantaneous Trip Time
~35 ms
Drop-out Time
~40 ms
Trip Time Delays for Phase Thresholds
Below descriptions are valid for tI>, tI>>, tI>>>.
DMT, Definite Minimum Time.
Setting Range: (0.01-150) s, step: 0.01 s.
IDMT, Inverse Definite Minimum Time.
Setting Range: TMS (Time Multiplier Setting): (0.025-3.2), step: 0.001.
Inverse Protection Curves available
IEC STI, IEC Short Time Inverse
IEC SI, IEC Standard Inverse
IEC VI, IEC Very Inverse
IEC EI, IEC Extreme Inverse
IEC LTI, IEC Long Time Inverse
SA, Semiconductor Protection
SB, Definite Inverse
SC (CO2), Short Time Inverse
SD (CO8), Long Time Inverse
SE (CO-C3H), Normal Inverse
IEEE MI, IEEE Moderately Inverse
IEEE VI, IEEE Very Inverse
IEEE EI, IEEE Extremely Inverse
Reset Time Delays for Phase Thresholds Below descriptions are valid for tI>, tI>>, tI>>>.
DMT, Definite Minimum Time.
Setting Range: (0.01-150) s, step: 0.01 s.
IDMT, Inverse Definite Minimum Time.
Setting Range: TMS (Time Multiplier Setting): (0.025-3.2), step: 0.001.
Measurement Technique
Fundamental harmonic.
Current Measurement Range
For Type T1 Protection: (0.1-40) I
en
, in 0.01 I
en
steps.
For Type T2 Protection: (0.02-5) I
en
, in 0.001 I
en
steps.
Current Threshold Setting Range
3 independent thresholds, set as multipliers of Ien.
Setting range for type T1: (0.1 - 40) Ien.
For T1 Ie> : (0.1 - 25) Ien, in 0.01 Ien steps.
For T1 Ie>> : (0.5 - 40) Ien, 0.01 Ien steps.
For T1 Ie>>> : (0.5 - 40) Ien, 0.01 Ien steps.
Setting range for type T2: (0.02 - 5) Ien.
For T2 Ie> : (0.02 - 5) Ien, 0.001 Ien steps.
For T2 Ie>> : (0.02 - 5) Ien, 0.001 Ien steps.
For T2 Ie>>> : (0.02 - 5) Ien, 0.001 Ien steps.
2 Protection Functions
2.1 Phase Overcurrent Protection [ANSI 50/51]
2.2 Earth Overcurrent Protection [ANSI 50N/51N]
Summary of Contents for CPM 310 G
Page 1: ...CPM 310 G Digital Overcurrent Protection Relay User Application Manual vEN 2016 03...
Page 2: ...2...
Page 6: ...6 ABOUT DEMA...
Page 11: ...11 INTRODUCTION...
Page 32: ...32 PACKING LABELING INFORMATION...
Page 34: ...34 OPERATING MANUAL...
Page 53: ...53 RELAY MENUS MANUAL...
Page 55: ...55 The Menu Tree...
Page 56: ...56...
Page 57: ...57...
Page 58: ...58...
Page 59: ...59...
Page 60: ...60...
Page 61: ...61...
Page 128: ...128 DIGICONNECT PC PROGRAM MANUAL...
Page 189: ...189 APPLICATION DIAGRAMS...
Page 191: ...191 Sample Power Transformer Protection Application Diagram...
Page 193: ...193 FUNDAMENTAL CABLING DIAGRAM...
Page 203: ...203 APPLICATION DIAGRAM NO 10 RS485 Cabling...
Page 204: ...204 TECHNICAL DATA...
Page 220: ...220 GLOSSARY...