- 213 -
Technical Characteristics
Record Details
Setting changes, trip records, disturbance records, alarms and other records are
saved with time & date stamps.
Time Information:
day / month / year, hour / minute / second / millisecond.
Distinguishing Time
1 ms
Recordings Quantity
151 records.
Record Structure
Record title and time stamp; amplitude, source and input & output status is
applicable.
Records Viewing
On the relay menus or over DigiConnect PC program.
Waveform Records Quantity
5 records.
Waveform Record Time
3 s each.
0.4 s record before trigger.
2.6 s record after trigger.
Record Form
Current oscillogram.
Records Viewing
PC program.
Trigger
Via an input or automatically by protection function pick-up.
Pick-up Current and Error
1.05 of threshold (1.6 of threshold for SA Semiconductor curve), error: ±0.1 I
s
Protection Threshold Error
±% 2
DMT and IDMT Delaying Error
±% 5 or ± 40 ms (One of the criteria will be fulfilled). Valid in the range (2 - 20) I
s
.
Measured current is max. 40 I
n
.
Thermal Trip Delaying Error
±% 5 or ± 200 ms (One of the criteria will be fulfilled). Valid in the range (1.5 - 8)
I
s
.
Measuring Error
±%1 at I = I
n
.
Primary Phase Nominal Current
Setting range: (1-9999) A, in steps of 1 A.
Secondary Phase Nominal Current
1 A or 5 A. Settings should be done along with dip-switch adjustment.
Primary Earth Nominal Current
Setting range: (1-9999) A, in steps of 1 A.
Secondary Earth Nominal Current
T1-1A, T1-5A, T2-1A or T2-5A. Settings should be done along with dip-switch
adjustment.
Dielectric Withstand
2,000 V / 50 Hz / 1 min and 2,200 V / 50 Hz / 1 s.
Mounting Options
Flush / rack mounting.
Case Construction
Socket and draw out construction, automatic secondary circuit bridging function.
Case Dimensions
144 mm x 179 mm x 200 mm (width x height x depth).
Case Level of Protection
Front side IP52, rear side and terminals IP20.
Storage & Operation Ambient Temp.
min. -25°C, max +70°C
Net Weight
3.5 kg
2.13 General Information
2.12 Current Transformer Compatibility
2.9 Event Records
Stamp Information
2.10 Waveform Records
Record Time Structure
2.11 Error Ratings
Summary of Contents for CPM 310 G
Page 1: ...CPM 310 G Digital Overcurrent Protection Relay User Application Manual vEN 2016 03...
Page 2: ...2...
Page 6: ...6 ABOUT DEMA...
Page 11: ...11 INTRODUCTION...
Page 32: ...32 PACKING LABELING INFORMATION...
Page 34: ...34 OPERATING MANUAL...
Page 53: ...53 RELAY MENUS MANUAL...
Page 55: ...55 The Menu Tree...
Page 56: ...56...
Page 57: ...57...
Page 58: ...58...
Page 59: ...59...
Page 60: ...60...
Page 61: ...61...
Page 128: ...128 DIGICONNECT PC PROGRAM MANUAL...
Page 189: ...189 APPLICATION DIAGRAMS...
Page 191: ...191 Sample Power Transformer Protection Application Diagram...
Page 193: ...193 FUNDAMENTAL CABLING DIAGRAM...
Page 203: ...203 APPLICATION DIAGRAM NO 10 RS485 Cabling...
Page 204: ...204 TECHNICAL DATA...
Page 220: ...220 GLOSSARY...