Default Settings
Default Settings
Communications Mode
USB
Protection
Active
Protocol
DEMCOM
Ie> (Threshold)
0.25 I
en
Baud rate
38,400
Delay Type
DMT
Relay Address
001
tI
e
>
1.00 s
Reset Type
DMT
Hour
GMT+02:00
tReset
0.04 s
Date
GMT+02:00
System Frequency
50 Hz
Protection
Active
Relay Description
DEMAROLE
Ie>> (Threshold)
0.75 I
en
Password
0000
Delay Type
DMT
Symbolization
rstn
tI
e
>>
0.05 s
Active Group
G1
Reset Type
DMT
Phase Rotation
RST
tReset
0.04 s
Backlight
Automatic
Language
English
Protection
Passive
Setting Password
Passive
Ie>>> (Threshold)
1.00 I
en
CB Password
Passive
Delay Type
DMT
tI
e
>>>
0.05 s
Primary Phase Nominal
60 A
Reset Type
DMT
Secondary Phase Nominal
5 A
tReset
0.04 s
Primary Earth Nominal
60 A
Secondary Earth Nominal
T1-5A
Protection
Passive
%(I2/I1)> (Threshold)
20%
t%(I
2
/I
1
)>
5.0 s
Level Percentage
200%
Time
1.0 s
Protection
Passive
Pickup tI>
Passive
I2> (Threshold)
0.5 I
n
Pickup tI>>
Passive
Delay Type
DMT
Pickup tI>>>
Passive
tI
2
>
5.0 s
Pickup tIe>
Passive
Reset Type
DMT
Pickup tIe>>
Passive
tReset
0.04 s
Pickup tIe>>>
Passive
Pickup tI2>
Passive
Protection
Passive
Pickup tI2>>
Passive
I2> (Threshold)
2.0 I
n
Delay Type
DMT
Output No.:
123456
tI
2
>
0.2 s
Trip
100000
Reset Type
DMT
I>
000000
tReset
0.04 s
tI>
000000
I>>
000000
Protection
Passive
tI>>
000000
Iθ> (Threshold)
1.0 I
n
I>>>
000000
T
e
20 minutes
tI>>>
000000
k
1.1
I
e
>
000000
Trip θ
100%
tI
e
>
000000
Alarm θ
Active
I
e
>>
000000
Alarm θ Threshold
80%
tI
e
>>
000000
I
e
>>>
000000
tI
e
>>>
000000
tI<
000000
Negative Sequence Overcurrent, I2> (ANSI 46)
Cold Load Pickup
Output Settings
Protection Settings, Group 2 (Continued)
Earth Overcurrent, Ie> (ANSI 50N/51N)
Negative Sequence Overcurrent, I2>> (ANSI 46)
Earth Overcurrent, Ie>>> (ANSI 50N/51N)
Automatic Control Settings
Thermal Overload, Iθ> (ANSI 49)
Communication Settings
System Settings
Current Transformer Settings
Earth Overcurrent, Ie>> (ANSI 50N/51N)
Broken Conductor, %(I2/I1)>
Summary of Contents for CPM 310 G
Page 1: ...CPM 310 G Digital Overcurrent Protection Relay User Application Manual vEN 2016 03...
Page 2: ...2...
Page 6: ...6 ABOUT DEMA...
Page 11: ...11 INTRODUCTION...
Page 32: ...32 PACKING LABELING INFORMATION...
Page 34: ...34 OPERATING MANUAL...
Page 53: ...53 RELAY MENUS MANUAL...
Page 55: ...55 The Menu Tree...
Page 56: ...56...
Page 57: ...57...
Page 58: ...58...
Page 59: ...59...
Page 60: ...60...
Page 61: ...61...
Page 128: ...128 DIGICONNECT PC PROGRAM MANUAL...
Page 189: ...189 APPLICATION DIAGRAMS...
Page 191: ...191 Sample Power Transformer Protection Application Diagram...
Page 193: ...193 FUNDAMENTAL CABLING DIAGRAM...
Page 203: ...203 APPLICATION DIAGRAM NO 10 RS485 Cabling...
Page 204: ...204 TECHNICAL DATA...
Page 220: ...220 GLOSSARY...