- 79 -
Thermal Alarm Θ
Just like
Trip Θ
,
Alarm Θ
is a heating threshold in
percentage; however,
Alarm Θ
function activates LEDs
and any possibly configured outputs to inform the
administrator to take appropriate precautions, instead
of tripping the circuit breaker.
Alarm Θ
setting can be
done within the range of %50 - %200, with the
limitation that
Alarm Θ
value cannot be set over the
Trip Θ
set value.
Alarm Θ
function can be set as
Active
or
Passive
via the
Alarm Θ
option.
Alarm Θ
function can be utilized in two ways.
When
Thermal Θ
measurement reaches
Alarm Θ
threshold, the user is notified via the static alarm LED
on the frontal face of CPM 310 G, while the alarming
situation is declared on the
Alarm Menu
. The use of
Alarm Menus
will be examined thoroughly on the
dedicated section in the following pages.
Alarm Θ function can also be utilized to automate
cooling systems or to inform the supervisor about the
situation remotely. If, e.g., a forced air cooling system
is to be driven when the protected power transformer
reaches a fixed heating percentage, a programmable
output with Alarm Θ function appointed can be
employed to generate a start signal to the
preconfigured appropriate circuit. If the Alarm Θ
notification is to be sent to the supervisor via an
auxiliary system, e.g. a GPRS communication system, a
programmable output with Alarm Θ function appointed
can be employed to provide notification signal to the
related device. Doing this, CPM 310 G will inform the
configured communications device to take appropriate
action when Alarm Θ threshold is reached. □
Summary of Contents for CPM 310 G
Page 1: ...CPM 310 G Digital Overcurrent Protection Relay User Application Manual vEN 2016 03...
Page 2: ...2...
Page 6: ...6 ABOUT DEMA...
Page 11: ...11 INTRODUCTION...
Page 32: ...32 PACKING LABELING INFORMATION...
Page 34: ...34 OPERATING MANUAL...
Page 53: ...53 RELAY MENUS MANUAL...
Page 55: ...55 The Menu Tree...
Page 56: ...56...
Page 57: ...57...
Page 58: ...58...
Page 59: ...59...
Page 60: ...60...
Page 61: ...61...
Page 128: ...128 DIGICONNECT PC PROGRAM MANUAL...
Page 189: ...189 APPLICATION DIAGRAMS...
Page 191: ...191 Sample Power Transformer Protection Application Diagram...
Page 193: ...193 FUNDAMENTAL CABLING DIAGRAM...
Page 203: ...203 APPLICATION DIAGRAM NO 10 RS485 Cabling...
Page 204: ...204 TECHNICAL DATA...
Page 220: ...220 GLOSSARY...