DMT: Definite Minimum Time Characteristic
DMT characteristic is used for obtaining constant trip and reset times. There are no parameters for the
DMT characteristic other than the constant trip or reset time. Characteristic notation is as follows:
e.g., t = DMT 0.25s.
The image below shows the DMT characteristics for given current values. □