Appendix B Accessories
|
VFD-B Series
B-38
Revision July 2008, BE16, SW V4.08 & V5.00
B.9 No-fuse Circuit Breaker Chart
For 1-phase/3-phase drives, the current rating of the breaker shall be within 2-4 times maximum input
current rating.
(Refer to Appendix A for rated input current)
1-phase 3-phase
Model
Recommended
no-fuse
breaker (A)
Model
Recommended
no-fuse
breaker (A)
Model
Recommended
no-fuse
breaker (A)
VFD007B21A 20 VFD007B23A
10 VFD220B23A
175
VFD015B21A/B 30 VFD007B43A
5 VFD220B43A
100
VFD022B21A 50
VFD007B53A
5 VFD220B53A
60
VFD015B23A/B
15
VFD300B23A
225
VFD015B43A
10
VFD300B43A
125
VFD015B53A
5
VFD300B53A
75
VFD022B23A
30
VFD370B23A
250
VFD022B43B
15
VFD370B43A
150
VFD022B53A
10
VFD370B53A
100
VFD037B23A
40
VFD450B43A
175
VFD037B43A
20
VFD450B53A
125
VFD037B53A
15
VFD550B43C
250
VFD055B23A
50
VFD550B53A
150
VFD055B43A
30
VFD750B43C
300
VFD055B53A
20
VFD750B53A
175
VFD075B23A
60
VFD075B43A
40
VFD075B53A
30
VFD110B23A
100
VFD110B43A
50
VFD110B53A
40
VFD150B23A
125
VFD150B43A
60
VFD150B53A
40
VFD185B23A
150
VFD185B43A
75
VFD185B53A
50