![Delta VFD-B User Manual Download Page 84](http://html1.mh-extra.com/html/delta/vfd-b/vfd-b_user-manual_2471887084.webp)
Chapter 5 Parameters
|
VFD-B Series
Revision July 2008, BE16, SW V4.08 & V5.00
5-27
Password Decode Flow Chart
3 chances to enter the correct
password.
1st time displays "01" if
password is incorrect.
2nd time displays "02", if
password is incorrect.
3rd time displays "P code"
(blinking)
If the password was entered
incorrectly after three tries,
the keypad will be locked.
Turn the power OFF/ON to
re-enter the password.
Incorrect Password
END
Displays 00 when
entering correct
password into
Pr.00-07.
00-08
00-07
00-07
Displays 00 when
entering correct
password into
Pr.00-07.
Correct Password
END
00-08
00 - 09
Control method
Factory Setting: 00
Settings
00
V/f
control
01
V/f + PG Control
02
Vector
Control
03
PG Control
This parameter determines the control method of the AC motor drive.
PG is encoder (Pulse Generator) feedback for which an option PG card is required.
00 - 10
Reserved