Chapter 5 Parameters
|
VFD-B Series
Revision July 2008, BE16, SW V4.08 & V5.00
5-39
02- 06
Line Start Lockout
Factory Setting: 00
Settings
00
Disable. Operation status is not changed even if operation
command source Pr.02-01 and/or Pr.02-14 is changed.
01
Enable. Operation status is not changed even if operation command
source Pr.02-01 and/or Pr.02-14 is changed.
02
Disable. Operation status will change if operation command source
Pr.02-01 and/or Pr.02-14 is changed.
03
Enable. Operation status will change if operation command source
Pr.02-01 and/or Pr.02-14 is changed.
This parameter determines the response of the drive when power is on and the operation
command source is changed.
Pr.02-06
Start lockout (Run when power is ON)
Operation status when operation
command source is changed
0
Disable (AC motor drive will run)
Keep previous status
1
Enable (AC motor drive won’t run)
Keep previous status
2
Disable (AC motor drive will run)
Change according to the new
operation command source
3
Enable (AC motor drive won’t run)
Change according to the new
operation command source
When the operation command source is from an external terminal and operation command is
ON (FWD/REV-DCM=close), the AC motor drive will operate according to Pr.02-06 after
power is applied.
<For terminals FWD and REV only>
1. When Pr.02-06 is set to 0 or 2, AC motor drive will run immediately.
2. When Pr.02-06 is set to 1 or 3, AC motor drive will remain stopped until operation
command is received after previous operation command is cancelled.