Appendix B Accessories
|
VFD-B Series
Revision July 2008, BE16, SW V4.08 & V5.00
B-33
575V, 50/60Hz, 3-Phase
Inductance (mH)
kW HP
Fundamental
Amps
Max.
continuous
Amps
3% impedance
5% impedance
0.75 1
2
3
20
32
1.5 2
4
6
9
12
2.2 3
4
6
9
12
3.7 5
8
12
5
7.5
5.5 7.5
8
12
3
5
7.5 10
12
18
2.5
4.2
11 15
18
27
1.5
2.5
15 20
25
37.5
1.2
1.8
18.5 25
25
37.5
1.2
1.8
22 30
35
52.5
0.8
1.2
30 40
45
67.5
0.7
1.2
37 50
55
82.5
0.5
0.85
45 60
80
120
0.4
0.7
55 75
80
120
0.4
0.7
75 100
100
150
0.3
0.45
B.6.2 AC Output Reactor Recommended Value
230V, 50/60Hz, 3-Phase
Inductance (mH)
kW HP
Fundamental
Amps
Max.
continuous
Amps
3% impedance
5% impedance
0.75
1 8
12
3
5
1.5
2 8
12
1.5
3
2.2
3 12
18
1.25
2.5
3.7
5 18
27
0.8
1.5
5.5
7.5 25
37.5
0.5
1.2
7.5
10 35
52.5
0.4
0.8
11
15 55
82.5
0.25
0.5
15
20 80
120
0.2
0.4
18.5
25 80
120
0.2
0.4
22
30 100
150
0.15
0.3
30
40 130
195
0.1
0.2
37
50 160
240
0.075
0.15