Appendix B Accessories
|
VFD-B Series
B-30
Revision July 2008, BE16, SW V4.08 & V5.00
B.4 Remote Controller RC-01
Dimensions are in millimeter
AFM ACM
+10V
AVI
DCMMI5 FWD REV JOG
8
6
5
4 16 15 14 13 11
RC-01
Terminal
block
(Wiring
connections)
VFD-B
I/O
Block
VFD-B Programming:
Pr.02-00 set to 1
Pr.02-01 set to 1 (external controls)
Pr.02-05 set to 1 (setting Run/Stop and Fwd/Rev controls)
Pr.04-08 (MI5) set to 05 (External reset)
NOTE: It needs to set the switch SW1 to SINK mode.