Chapter 5 Parameters
|
VFD-B Series
5-4
Revision July 2008, BE16, SW V4.08 & V5.00
Parameter Explanation
Settings
Factory
Setting
Customer
01-21 Decel Time 4
0.01 to 3600.0 sec
10.0
01-18 ~ 01-21: Factory setting for models of 30hp (22kW) and above is 60sec.
01-22 Jog
Deceleration
Time
0.1 to 3600.0 sec
1.0
00: Unit: 1 sec
01: Unit: 0.1 sec
01-23
Accel/Decel Time
Unit
02: Unit: 0.01 sec
01
Group 2 Operation Method Parameters
Parameter Explanation
Settings
Factory
Setting
Customer
00: Digital keypad (PU01) UP/DOWN keys or
Multi-function Inputs UP/DOWN. Last
used frequency saved.
01: 0 to +10V from AVI
02: 4 to 20mA from ACI
03: -10 to +10Vdc from AUI
04: RS-485 serial communication (RJ-11).
Last used frequency saved.
05: RS-485 serial communication (RJ-11).
Last used frequency not saved.
02-00
Source of First
Master Frequency
Command
06: Combined use of master and auxiliary
frequency command
(See Pr. 02-10 to 02-12)
00
00: Digital keypad (PU01)
01: External terminals. Keypad STOP/RESET
enabled.
02: External terminals. Keypad STOP/RESET
disabled.
03: RS-485 serial communication (RJ-11).
Keypad STOP/RESET enabled.
02-01
Source of First
Operation Command
04: RS-485 serial communication (RJ-11).
Keypad STOP/RESET disabled.
00
00: STOP: ramp to stop; E.F.: coast to stop
01: STOP: coast to stop; E.F.: coast to stop
02: STOP: ramp to stop; E.F.: ramp to stop
02-02 Stop
Method
03: STOP: coast to stop; E.F.: ramp to stop
00
230V&460V:
1-5hp/0.75-3.7kW: 1-15kHz
15
7.5-25hp/5.5-18.5kW: 01-15kHz
09
30-60hp/22-45kW: 01-09kHz
06
75-100hp/55-75kW: 01-06kHz
06
575V:
1-15hp/0.75-11kW: 01-10 kHz
06
20-60hp/15-45kW: 01-08 kHz
06
02-03
PWM Carrier
Frequency
Selections
75-100hp/55-75kW: 01-06kHz
06