Chapter 5 Parameters
|
VFD-B Series
Revision July 2008, BE16, SW V4.08 & V5.00
5-35
02 - 14
Source of Second Operation Command
Factory Setting: 00
Settings
00
Digital keypad (PU01)
01
External terminals. Keypad STOP/RESET enabled.
02
External terminals. Keypad STOP/RESET disabled.
03
RS-485 serial communication (RJ-11). Keypad STOP/RESET
enabled.
04
RS-485 serial communication (RJ-11). Keypad STOP/RESET
disabled.
When the AC motor drive is controlled by external terminal, please refer to Pr.02-05 for details.
The first /second frequency/operation command is enabled/disabled by Multi Function Input
Terminals. Please refer to of Pr.04-04 ~ 04-09.
02 - 10
Source of the Master Frequency Command
Factory Setting: 00
Settings
00
Digital keypad (PU01) UP/DOWN keys or Multi-function Inputs
UP/DOWN. Last used frequency saved.
01
AVI 0 ~ +10VDC
02
ACI 4 ~ 20mA
03
AUI -10 ~ +10VDC
04
RS-485 serial communication (RJ-11). Last used frequency saved.
02 - 11
Source of the Auxiliary Frequency Command
Factory Setting: 00
Settings
00
Digital keypad (PU01) UP/DOWN keys or Multi-function Inputs
UP/DOWN. Last used frequency saved.
01
AVI 0 ~ +10VDC
02
ACI 4 ~ 20mA
03
AUI -10 ~ +10VDC
04
RS-485 serial communication (RJ-11). Last used frequency saved.
02 - 12
Combination of the Master and Auxiliary Frequency
Command
Factory Setting: 00
Settings
00
Master fre Auxiliary frequency
01
Master frequency - Auxiliary frequency
These three parameters (Pr.02-10~02-12) are enabled when Pr.02-00 or Pr.02-13 are set to
06. If they are enabled, the frequency command will be determined by these parameters.