Chapter 5 Parameters
|
VFD-B Series
5-16
Revision July 2008, BE16, SW V4.08 & V5.00
Parameter
Explanation
Settings
Factory
Setting
Customer
09-05 Reserved
09-06 Reserved
09-07 Response
Delay
Time
00 ~ 200 msec
00
Group 10 PID Control Parameters
Parameter
Explanation
Settings
Factory
Setting
Customer
00: Inhibit PID operation
01: Negative PID feedback from external
terminal (AVI) 0 to +10V
02: Negative PID feedback from external
terminal (ACI) 4 to 20mA
03: Positive PID feedback from external
terminal (AVI) 0 to +10V
10-00
Input terminal for
PID Feedback
04: Positive PID feedback from external
terminal (ACI) 4 to 20mA
00
10-01
Gain over PID
Detection value
0.00 to 10.00
1.00
10-02
Proportional Gain (P) 0.0 to 10.0
1.0
10-03 Integral
Gain
(I)
0.00 to 100.00 sec (0.00=disable)
1.00
10-04
Derivative Control
(D)
0.00 to 1.00 sec
0.00
10-05
Upper Bound for
Integral Control
00 to 100%
100
10-06
Primary Delay Filter
Time
0.0 to 2.5 sec
0.0
10-07
PID Output Freq
Limit
0 to 110%
100
10-08
Feedback Signal
Detection Time
0.0 to 3600.0 sec
60.0
00: Warn and keep operation
01: Warn and RAMP to stop
10-09
Treatment of the
Erroneous Feedback
Signals
02: Warn and COAST to stop
00
10-10
PG Pulse Range
1 to 40000
600
00: Disable PG
01: Single phase
02: Forward / Counterclockwise rotation
10-11 PG
Input
03: Reverse / Clockwise rotation
00
10-12
ASR (Auto Speed
Regulation) control
(with PG only) (P)
0.0 to 10.0
1.0