Chapter 5 Parameters
|
VFD-B Series
5-34
Revision July 2008, BE16, SW V4.08 & V5.00
Group 2: Operation Method Parameters
02 - 00
Source of First Master Frequency Command
Factory Setting: 00
Settings
00
Digital keypad (PU01) UP/DOWN keys or Multi-function Inputs
UP/DOWN. Last used frequency saved.
01
AVI 0 ~ +10VDC
02
ACI 4 ~ 20mA
03
AUI -10 ~ +10VDC
04
RS-485 serial communication (RJ-11). Last used frequency saved.
05
RS-485 serial communication (RJ-11). Last used frequency not
saved.
06
Combined use of master and auxiliary frequency command
See Pr. 02-10 to 02-12
02 - 13
Source of Second Master Frequency Command
Factory Setting: 00
Settings
00
Digital keypad UP/DOWN keys or Multi-function Inputs UP/DOWN.
Last used frequency saved.
01
AVI 0 ~ +10VDC
02
ACI 4 ~ 20mA
03
AUI -10 ~ +10VDC
04
RS-485 serial communication (RJ-11). Last used frequency saved.
05
RS-485 serial communication (RJ-11). Last used frequency not
saved.
06
Combined use of master and auxiliary frequency command
See Pr. 02-10 to 02-12
These parameters set the Master Frequency Command Source of the AC motor drive.
02 - 01
Source of First Operation Command
Factory Setting: 00
Settings
00
Digital
keypad
(PU01)
01
External terminals. Keypad STOP/RESET enabled.
02
External terminals. Keypad STOP/RESET disabled.
03
RS-485 serial communication (RJ-11). Keypad STOP/RESET
enabled.
04
RS-485 serial communication (RJ-11). Keypad STOP/RESET
disabled.