Chapter 5 Parameters
|
VFD-B Series
Revision July 2008, BE16, SW V4.08 & V5.00
5-3
Parameter Explanation
Settings
Factory
Setting
Customer
00-10 Reserved
Group 1 Basic Parameters
Parameter Explanation
Settings
Factory
Setting
Customer
01-00
Maximum Output
Frequency (Fmax)
50.00 to 400.00 Hz
60.00
01-01
Maximum Voltage
Frequency (Fbase)
0.10 to 400.00 Hz
60.00
230V series: 0.1V to 255.0V
220.0
460V series: 0.1V to 510.0V
440.0
01-02
Maximum Output
Voltage (Vmax)
575V series: 0.1V to 637.0V
575.0
01-03
Mid-Point Frequency
(Fmid)
0.10 to 400.00 Hz
0.50
230V series: 0.1V to 255.0V
1.7
460V series: 0.1V to 510.0V
3.4
01-04
Mid-Point Voltage
(Vmid)
575V series: 0.1V to 637.0V
4.8
01-05
Minimum Output
Frequency (Fmin)
0.10 to 400.00 Hz
0.50
230V series: 0.1V to 255.0V
1.7
460V series: 0.1V to 510.0V
3.4
01-06
Minimum Output
Voltage (Vmin)
575V series: 0.1V to 637.0V
4.8
01-07
Output Frequency
Upper Limit
1 to 120%
100
01-08
Output Frequency
Lower Limit
0 to100 %
0
01-09 Accel Time 1
0.01 to 3600.0 sec
10.0
01-10 Decel Time 1
0.01 to 3600.0 sec
10.0
01-11 Accel Time 2
0.01 to 3600.0 sec
10.0
01-12 Decel Time 2
0.01 to 3600.0 sec
10.0
01-09 ~ 01-12: Factory setting for models of 30hp (22kW) and above is 60sec.
01-13 Jog
Acceleration
Time
0.1 to 3600.0 sec
1.0
01-14 Jog Frequency
0.10 Hz to 400.00 Hz
6.00
00: Linear Accel/Decel
01: Auto Accel, Linear Decel
02: Linear Accel, Auto Decel
03: Auto Accel/Decel (Set by load)
01-15
Auto acceleration /
deceleration (refer to
Accel/Decel time
setting)
04: Auto Accel/Decel (set by Accel/Decel
Time setting)
00
01-16
Acceleration S-
Curve
00 to 07
00
01-17
Deceleration S-
Curve
00 to 07
00
01-18 Accel Time 3
0.01 to 3600.0 sec
10.0
01-19 Decel Time 3
0.01 to 3600.0 sec
10.0
01-20 Accel Time 4
0.01 to 3600.0 sec
10.0