Chapter 5 Parameters
|
VFD-B Series
5-92
Revision July 2008, BE16, SW V4.08 & V5.00
Content Address
Function
12: Current exceeds 2 times rated current during steady state
operation (ocn)
13: Ground Fault (GFF)
14: Low voltage (Lv)
2100H
15: CPU failure 1 (cF1)
16: CPU failure 2 (cF2)
17:
Base
Block
18:
Overload
(oL2)
19: Auto accel/decel failure (cFA)
20: Software protection enabled (codE)
21: EF1 Emergency stop
22:
PHL
(Phase-Loss)
23: cEF (Preliminary count value attained, EF active)
24:
Lc
(Under-current)
25: AnLEr (Analog feedback signal error)
26: PGErr (PG feedback signal error)
Status of AC drive
LED: 0: light off, 1: light up
00: RUN LED
01: STOP LED
02: JOG LED
03: FWD LED
2101H
Bit 0-4
04: REV LED
Bit 5
0: F light off, 1: F light on
Bit 6
0: H light off, 1: H light on
Bit 7
0: “u” light off, 1: “u” light on
Bit 8
1: Master frequency Controlled by communication
interface
Bit 9
1: Master frequency controlled by analog signal
Bit 10
1: Operation command controlled by
communication interface
Bit 11
1: Parameters have been locked
Bit 12
0: AC drive stops, 1: AC drive operates
Bit 13
1: Jog command
Bit 14-15
Reserved
2102H
Frequency command (F)
2103H
Output
frequency
(H)
2104H
Output
current
(AXXX.X)
2105H
DC-BUS Voltage (UXXX.X)
2106H
Output voltage (EXXX.X)
2107H
Step number of Multi-Step Speed Operation
2108H
Step number of PLC operation
2109H
Content of external TRIGGER
210AH
Power factor angle
Status
monitor
Read only
210BH
Estimated torque ratio (XXX.X)
210CH
Motor
speed
(rpm)
210DH
PG pulse (low word) /unit time (Pr.10-15)
210EH
PG pulse (high word) /unit time (Pr.10-15)
210FH
Output power (KW)
2110H
Reserved
2200H
Feedback Signal (XXX.XX %)