Chapter 5 Parameters
|
VFD-B Series
5-44
Revision July 2008, BE16, SW V4.08 & V5.00
03 - 10
Desired Frequency Attained 2
Unit: 0.01
Settings 0.00 to 400.00 Hz
Factory Setting: 0.00
If a multi-function output terminal is set to function as Desired Frequency Attained 1 or 2
(Pr.03-00 to Pr.03-03 = 09 or 22), then the output will be activated when the programmed
frequency is attained.
- 2Hz
4Hz
2Hz
OFF
OF F
ON
ON
OF F
ON
OFF
ON
OFF
OFF
O N
OFF
ON
ON
detection
range
Fr equ ency
ma ster
fre quency
des ir ed
frequency
detection range
dete ction
ran ge
DC br ake time
dur ing stop
Time
waiting time
for
freque ncy
run/s to p
master fr eq. attained
(output signal)
des ire d fr eq. attaine d
settin g 03 ze ro spee d indica tion
se tting 24 zero sp eed indi cation
out put timing chart o f m ultip le func tion ter minals
wh en setti ng to fr equ en cy at tain ed or z ero spe ed in di cation
03 - 05
Analog Output Signal (AFM)
Factory Setting: 00
Settings
00
Analog Frequency Meter (0 to Maximum Output Frequency)
01
Analog Current Meter (0 to 250% of rated AC motor drive current)
02
Output voltage (0 to Pr.01-02)
03
Output frequency command (0 to Maximum Frequency)
04
Output motor speed (0 to the Maximum Frequency)
05
Load power factor (cos90
o
to 0
o
)
This parameter sets the function of the AFM output 0~+10VDC (ACM is common).
03 - 06
Analog Output Gain
Unit: 1
Settings
01 to 200%
Factory Setting: 100
This parameter sets the voltage range of the analog output signal.