Chapter 5 Parameters
|
VFD-B Series
Revision July 2008, BE16, SW V4.08 & V5.00
5-23
5.3 Description of Parameter Settings
Group 0: User Parameters
: This parameter can be set during operation.
00 - 00
Identity Code of the AC motor drive
Settings
Read Only
Factory setting: ##
00 - 01
Rated Current Display of the AC motor drive
Settings
Read Only
Factory setting: #.#
Pr. 00-00 displays the identity code of the AC motor drive. The capacity, rated current, rated
voltage and the max. carrier frequency relate to the identity code. Users can use the following
table to check how the rated current, rated voltage and max. carrier frequency of the AC motor
drive correspond to the identity code.
Pr.00-01 displays the rated current of the AC motor drive. By reading this parameter the user
can check if the AC motor drive is correct.
230V Series
kW 0.75
1.5
2.2
3.7
5.5
7.5
11
15
18.5
22
30
37
HP 1.0
2.0
3.0
5.0
7.5
10
15
20
25
30
40
50
Pr.00-00 04 06 08
10
12
14
16 18
20
22
24
26
Rated Output
Current (A)
5.0 7.0 11
17
25
33
49 65
75
90
120
146
Max. Carrier
Frequency
15kHz 9
kHz
460V Series
kW 0.75
1.5
2.2 3.7 5.5 7.5
11
15 18.5
22
30
37
45
55
75
HP 1.0
2.0
3.0 5.0 7.5
10
15
20
25
30
40
50
60
75 100
Pr.00-00 05 07 09
11
13
15
17
19
21 23
25
27
29
31
33
Rated Output
Current (A)
2.7 4.2 5.5 8.5
13
18
24
32
38 45
60
73
91
110 150
Max. Carrier
Frequency
15 kHz
9 kHz
6 kHz
575V Series
kW 0.75
1.5
2.2
3.7 5.5 7.5
11
15 18.5
22
30
37
45
55
75
HP
1.0 2.0 3.0
5.0 7.5
10
15
20
25 30
40
50
60
75 100
Pr.00-00
100 101 102 103 104 105 106 107 108 109 110 111 112 113 114
Rated Output
Current (A)
1.7 3.5 4.5
7.5
10 13.5 19
22
27 34
41
52
62
80 100
Max. Carrier
Frequency
10 kHz
8 kHz
6 kHz