Chapter 5 Parameters
|
VFD-B Series
5-38
Revision July 2008, BE16, SW V4.08 & V5.00
02 - 04
Motor Direction Control
Factory Setting: 00
Settings
00
Enable Forward/Reverse operation
01
Disable Reverse operation
02
Disabled Forward operation
The parameter determines the AC motor drive direction of rotation. See Chapter 2 for definition
of direction of rotation.
02 - 05
2-wire/ 3-wire Operation Control Modes
Factory Setting: 00
Settings
00
2-wire: FWD/STOP, REV/STOP
01
2-wire:
FWD/REV,
RUN/STOP
02
3-wire
Operation
There are three different types of control modes:
02-05
External Terminal
00
2-wire
FWD /STOP
REV / STOP
VFD-B
FWD:("OPEN":STOP)
("CLOSE":FWD)
REV:("OPEN": STOP)
("CLOSE": REV)
DCM
FWD/STOP
REV/STOP
01
2-wire
FWD/ REV
RUN / STOP
VFD-B
FWD:("OPEN":STOP)
("CLOSE":RUN)
REV:("OPEN": F
("CLOSE": REV)
DCM
RUN/STOP
FWD/REV
WD)
02 3-wire
VFD-B
FWD:("CLOSE":RUN)
EF: ("OPEN":STOP)
REV:("OPEN": F
("CLOSE": REV)
DCM
STOP
RUN
REV/FWD
WD)