05 Optional Accessories | REG2000
5-4
KPC-CC01 & KPC-CE01 Dimensions
Unit: mm [inch]
Optional digital keypad RJ45 extension cable
No.
Part No.
L
mm
inch
1 UC-CMC003-01A
300
11.8
2 UC-CMC005-01A
500
19.6
3 UC-CMC010-01A
1000
39
4 UC-CMC015-01A
1500
59
5 UC-CMC020-01A
2000
78.7
6 UC-CMC030-01A
3000
118.1
7 UC-CMC050-01A
5000
196.8
8 UC-CMC100-01A
10000
393.7
9 UC-CMC200-01A
20000
787.4
The Power Regenerative Unit is controlled by an external terminal MIx by default. You can also
control the Power Regenerative Unit from the keypad.
1. Control from the digital keypad:
Set Pr.01-04 = 2 to change to the digital keypad as the operation command source.
2. Control by an external terminal (default: MI1):
Set Pr.01-04 = 1 to change to the external terminals as the operation command source.
The Power Regenerative Unit activation level is determined by the voltage level. It is not
necessary to unplug and reconnect the external terminals.