07 Descriptions of Parameter Settings | REG2000
2
Display the low word of the kilowatt hours (kWh) regenerated by REG2000
Default:
###.#
Settings
0.0–999.9
Display the high word of the kilowatt hours (kWh) regenerated by REG2000
Default:
####
Settings
0–9999
When Pr.03-12 = 1, Pr.00-09 and Pr.00-10 are reset to 0 and Pr.03-12 returns to 0.
After you set Pr.00-09 and Pr.00-10, the REG starts to run and the counting begins.
It displays by Pr.00-10 * 1000 + Pr.00-09.
Display highest internal ambient temperature (°C) (air outlet)
Display highest power module’s temperature (°C)
Default:
##.#
Settings
Read-only
Display internal ambient temperature (°C) (air outlet)
Display power module's temperature (°C)
Default:
##.#
Settings
Read-only
Display digital input ON/OFF status
Display digital output ON/OFF status
Default:
###
Settings
Read-only
DC BUS voltage during a malfunction (V
DC
)
Default:
##.#
Settings
Read-only
Mains frequency during a malfunction (Hz)
Current during a malfunction (A)
Default:
#.##
Settings
Read-only
Fault record 1
Fault record 2
Fault record 3
Fault record 4
Fault record 5
Fault record 6
Default:
0
Settings
0: no error record