04 Wiring | REG2000
4-14
Frame C
Main Circuit Terminals
-/DC- +/DC+ R/L1 S/L2 T/L3
REG2000 Frame C
Model Name
Terminals: R/L1, S/L2, T/L3, -/DC+, +/DC+
Terminals:
Maximum
Wire
Gauge
Minimum
Wire
Gauge
Screw Size
Tightening
Torque
(±10%)
Maximum
Wire
Gauge
Minimum
Wire
Gauge
Screw Size
Tightening
Torque
(±10%)
REG300A23A-21
50 mm²
[1/0 AWG]
35 mm²
[2 AWG]
M8
81.5 kg-cm
(70.8 lb-in.)
(8 N-m)
35 mm²
[2 AWG
16 mm²
[6 AWG]
M8
81.5 kg-cm
(70.8 lb-in.)
(8 N-m)
REG370A23A-21
50 mm²
[1/0 AWG]
50 mm²
[1/0 AWG]
25 mm²
[4 AWG]
REG370A43A-21
25 mm²
[4 AWG]
25 mm²
[4 AWG]
16 mm²
[6 AWG]
REG450A43A-21
25 mm²
[4 AWG]
25 mm²
[4 AWG]
16 mm²
[6 AWG]
REG550A43A-21
35 mm²
[2 AWG]
35 mm²
[2 AWG]
16 mm²
[6 AWG]
If you install at Ta 50°C environment, select copper wire with voltage rating of 600 V and
temperature resistance of 75°C or 90°C.
If you install at Ta 50°C above environment, select copper wire with voltage rating of 600 V and
temperature resistance of 90°C or above.
For UL installation compliance, use copper wires when installing. The wire gauge is based on a
temperature resistance of 75°C, in accordance with UL requirements and recommendations. Do
not reduce the wire gauge when using high-temperature resistant wires.
Unit: mm
AWG VENDOR
VENDOR
P/N
A
(MAX.)
B
(MAX.)
C
(MIN.)
D
(MAX.)
d2
(MIN.)
E
(MIN.)
F
(MIN.)
W
(MAX.)
t
(MAX.)
6
KST
RNB14-8
40.0 11.0 9.5 22.0 8.3 13.0 11.0 24.0 2.5
4 RNB22-8
2 RNBS38-8
1/0 RNB60-8