04 Wiring | REG2000
4-18
MI1
E24V
COM
MO1
MI5
MI3
MO2
MCM
MI4
DCM
MI2
SG-
SG+
RB1
RC1
RA1
OP
E
N
485
485
120
(A)
(B)
Control Terminal Specifications
Function
Wire Size
Tightening
Torque
(±10%)
Group
Conductor
Stripping
Length
Minimum
Wire Gauge
Maximum
Wire Gauge
Control
Terminal
A
Solid/Strand
6 mm
0.2 mm²
[26 AWG]
1.5 mm²
[16 AWG]
5.1 kg-cm
[4.42 lb-in.]
[0.5 Nm]
B
5.6 kg-cm
[4.86 lb-in.]
[0.55 Nm]
To set to auto-mode without a keypad, wire the Power Regenerative Unit to go through a
multi-function input terminal (MIx, default setting is MI1) to connect to the terminal DCM.
Wiring notes:
The default for E24V-COM is short circuit and SINK mode (NPN). Refer to Diagram 1 in
Section 4-1 Wiring Diagram.
Terminal
Function Description
Default (NPN mode)
E24V
The default for +24 V-COM is
short circuit and SINK mode
(NPN) (Source).
+24 V ± 5% 200 mA
COM
Common terminal for digital
control signals (Sink)
Common terminal for multi-function inputs
MI1
–
MI5
Multi-function input 1–5
Refer to Pr.02-00–Pr.02-04 to program the
multi-function inputs MI1–MI5.
ON: the activation current is 6.5 mA
11 V
DC
;
OFF: leakage current tolerance is 10
μ
A
5 V
DC
DCM
Common terminal for digital
control signals (Sink)
Common terminal for multi-function inputs
MO1
Multi-function output 1 (photo
coupler)
The Power Regeneration Unit releases various monitor
signals, using a transistor (open collector).