05 Optional Accessories | REG2000
5-10
5-3 Fuse Specification Chart
Use UL certified fuses for short circuit protection. For installation in the United States, branch circuit
protection must be provided in accordance with the National Electrical Code (NEC) and any
applicable local codes. Use UL classified fuses to fulfill this requirement.
For installation in Canada, branch circuit protection must be provided in accordance with
Canadian Electrical Code and any applicable provincial codes. Use UL classified fuses to fulfill this
requirement.
See Section 4-1 Wiring Diagram for fuse installation.
Frame A
Frame B
Frame C
Model No.
Ampere
Model No.
Ampere
Model No.
Ampere
REG075A23A-21 50 REG150A23A-21
100 REG300A23A-21 200
REG110A23A-21 80 REG185A23A-21
125 REG370A23A-21 250
REG075A43A-21 25 REG220A23A-21
150 REG370A43A-21 125
REG110A43A-21 45 REG185A43A-21
60 REG450A43A-21 150
REG150A43A-21 50 REG220A43A-21
80 REG550A43A-21 200
REG300A43A-21
100