07 Descriptions of Parameter Settings | REG2000
7-5
After password protection is enabled, all parameter values except for Pr.01-03 display 0.
You can disable password protection by unlocking the password protection in Pr.01-02 and setting
this parameter to 0. Password protection remains off after a system reboot.
Otherwise, the password remains permanently active. After you turn on the system, you must first
unlock the password protection in Pr.01-02 before changing any parameters.
To reactivate password protection:
Method 1: Reenter the password in Pr.01-03.
Method 2: Reboot the system to immediately restore the password protection.
Method 3: Enter any value other than the password in Pr.01-02.
01-03
Decoding flowchart
01-03
Password setup
01-02
Lost password
Enter the correct password
at parameter 01-03, 01-03
will display 01
Enter the correct password
at parameter 01-02, 01-03
will display 00
Enter 9999 twice to
reset the password to
the factory default
01-02
01-02
01-03
Password incorrect
Password correct
Enter the correct
password at
parameter 01-02,
01-03 will display 00
There are only three attempts to enter the
correct password.
After the first incorrect attempt, the display
will show 01, after the second incorrect
attempt, the display will show 02, and after
the third incorrect attempt, a blinking
"P code" will be displayed, and after the third
incorrect attempt, a blinking "P code" will be
displayed.
The panel will be locked after three incorrect
password attempts, the system must be
restarted before the password can be
entered again.
Operation command source
Default:1
Settings 1: controlled by external terminals
2: controlled through the communication interface or the digital keypad
(KPC-CE01/KPC-CC01)
The standard REG package does not contain the digital keypad and you must control operation with
external terminals. Confirm that the wiring between multi-function input terminals is correct before
using.
To operate using the communication interface, you must purchase a digital keypad KPC-CC01 or
KPC-CE01 before you can set the operation command source to the communication interface.