02 Checking & Recommendations | REG2000
2-3
a
a
b
b
NOT E
※
The specified distances are only applicable in open spaces. As shown
in the diagram on the left, if the units are being installed in an enclosed
space, such as distribution channel or chassis, install ventilation or air
conditioning systems to keep the ambient temperature under the
operating temperature.
※
The table shows the required airflow rate for each model when
installing single units in an enclosed space. For multiple units, multiply
the required airflow rate by the number of units installed.
※
Refer to the “Airflow Rate for Cooling” table below when selecting and
designing ventilation systems.
※
Refer to the “Power Dissipation of REG” table below for the design of
air conditioning systems.
Airflow Rate for Cooling
Model No.
Flow Rate (cfm)
Flow Rate (m
3
/hr)
External
Internal Total External
Internal Total
REG075A23A-21
44 - 44 75 - 75
REG110A23A-21
44 - 44 75 - 75
REG150A23A-21
92 - 92 155 - 155
REG185A23A-21
92 - 92 155 - 155
REG220A23A-21
92 - 92 155 - 155
REG300A23A-21
121 - 121
206 - 206
REG370A23A-21
118 15 133 201 25 226
REG075A43A-21
44 - 44 75 - 75
REG110A43A-21
44 - 44 75 - 75
REG150A43A-21
44 - 44 75 - 75
REG185A43A-21
92 - 92 155 - 155
REG220A43A-21
92 - 92 155 - 155
REG300A43A-21
92 - 92 155 - 155
REG370A43A-21
121 - 121
206 - 206
REG450A43A-21
118 15 133 201 25 226
REG550A43A-21
118 15 133 201 25 226
※
The table shows the required airflow rate for each model when installing single units in an enclosed
space.
※
For multiple units, multiply the required airflow rate for single-unit installation by the number of units
installed.