07 Descriptions of Parameter Settings | REG2000
7-15
04 Communication Parameters
You can set this parameter during operation.
When using the communication interface, the
diagram on the right shows the communication
port pin definitions. We recommend that you
connect the Power Regenerative Unit to your PC
by using Delta IFD6530 or IFD6500 as a
communication converter.
Communication address
Default:
1
Settings 1–254
When the system uses the RS-485 serial communication interface for control or monitoring, every
Power Regenerative Unit must have its own communication address and every address in the
network must be unique.
COM1 transmission speed
Default:
9.6
Settings 4.8–115.2
Kbps
Sets the transmission speed between the Power Regenerative Unit and computers.
COM1 transmission fault treatment
Default:
3
Settings 0: Warn and continue operation
1: Warn and ramp to stop
2:
Reserved
3: No actions and no display
Specifies how the Power Regenerative Unit handles a transmission time-out error (such as a broken
line) during communications.
COM1 time-out detection
Default:
0.0
Settings 0.0–100.0
sec.
0.0: No detection
Sets the duration for a transmission time-out between communication ports and COM1.
COM1 communication protocol
Default:
1
Settings 0: 7, N, 1 for ASCII
1: 7, N, 2 for ASCII
2: 7, E, 1 for ASCII
3: 7, O, 1 for ASCII
4: 7, E, 2 for ASCII
5: 7, O, 2 for ASCII
6: 8, N, 1 for ASCII