07 Descriptions of Parameter Settings | REG2000
10
(MI1–5) to malfunction (except counting inputs). This parameter significantly improves these
situations, but response time is slightly delayed.
Digital Input direction
Default: 0
Settings 0–65535
Sets the activation level for input signals, and has no relation to the terminal’s SINK/SOURCE
status.
bits 0–4 correspond to MI1–MI5, respectively.
Enter corresponding values through communications to alter the ON/OFF status of the terminals.
Multi-function output 1 (Relay 1)
Default:4
Multi-function output 2 (MO1)
Default:3
Multi-function output 3 (MO2)
Default:
0
Settings
0: No function
1: Regenerate indicator
2: Run indicator
3: Ready indicator
4: Error indicator
5: No function
6: Warn indicator
7: No function
Includes the necessary external terminal output functions as required.
The following table lists the multi-function output terminal functions.
Setting
Function
Description
0
No function
The output terminal does not have any function.
1 Regenerate
indicator
When the Power Regenerative Unit is in Regenerate status,
the contacts are in ON status.
2 Run
indicator
After powering on and sending the RUN command, the Power
Regenerative Unit is in normal operation (including standby
and regenerate) and the contacts are in ON status.
3 Ready
indicator
The contacts are ON when there are no Power Regenerative
Unit errors or warnings. (When the phase lock is completed,
you can now send the RUN command.)
4 Error
indicator
The contacts are ON when the Power Regenerative Unit
detects an error.
5
No function
The output terminal does not have any function