04 Wiring | REG2000
4-9
3) Loosen the screws to wire the main circuit terminals.
Frame A, screw torque: 6–8 kg-cm [5.2–6.9 lb-in.] (0.59–0.78 Nm)
Frame B, screw torque: 14–16 kg-cm [12.15–13.88 lb-in.] (1.37–1.57 Nm)
Frame C, screw torque: 10–12 kg-cm [8.68–10.42lb-in.] (0.98–1.18 Nm)
Frame A, B Frame C
Main Circuit Terminal Diagram
R(L1)
S(L2)
T(L3)
R(L1)
S(L2)
T(L3)
Provides three-phase power input
DC+
DC-
Applicable to frames A - C
Terminal labels
Descriptions
R/L1, S/L2, T/L3 AC power input terminals (three-phase)
DC+, DC-
Connect to the AC motor drive’s terminals DC+ and DC- respectively. There is a
built-in fuse in the internal hardware circuit, which can prevent damage to the AC
motor drive if the REG malfunctions.
Ground connection. Comply with local regulations.