07 Descriptions of Parameter Settings | REG2000
4
01 Basic Parameters
You can set this parameter during operation.
Reset parameters
Default:
0
Settings 0: no function
1: parameter cannot be written
10: parameter reset
1: You can only adjust Pr.01-00–Pr.01-03, and the other parameters are read-only. In
combination with the password parameters, this prevents the parameters from being altered by
mistake.
10: Restores the parameters to the defaults. If a password is set, you must enter it before
restoring the parameter settings, and the password is cleared at the same time.
Select start-up display
Default:
0
Settings 0: mains frequency
1: DC BUS voltage
(
V
DC
)
2: Output current
(A
AC
)
Enter parameter protection password
Default:
0
Settings
1–9998,10000–65535
Display
value
0–2: number of incorrect passwords entered
Enter the password set in Pr.01-03 into Pr.01-02 to unlock all the password protected parameters.
After setting this parameter, write down the setting to avoid being locked out in the future.
Using parameters Pr.01-02 and Pr.01-03 prevents non-technicians from accidently altering other
parameters.
If you lose or forget the password, you can reset it by entering 9999 and pressing the "ENTER" key,
enter 9999 and press "ENTER" again (this sequence must be completed within 10 seconds;
otherwise, you have to do it again). This also restores all parameters back to the defaults.
Set parameter protection password
Default:
0
Settings
1–9998,10000–65535
Display
value
0: password not set or password entered successfully in Pr.01-02
1: parameters locked
This parameter sets the password protection, which you can enter directly the first time. After you
set the password, this parameter value becomes 1, meaning that password protection is enabled. To
make changes to any parameter, first enter the correct password in Pr.01-02. After you unlock the
password protection, the Pr.01-02 is reset to 0, and you can set all parameters.