D P M – C 5 3 0 O p e r a t i o n M a n u a l
5 - 6 4
_5
464
41125
Alarm time of over
current demand
Hour: 00–23
Minute: 00–59
byte
Hour,
Minute
2
R
465
41126
Second: 00–59
word Second
466
41127
Alarm status of over
active power demand
0: Cleared
1: Triggered
word
2
R
467
41128
Alarm times of over
active power demand
1–255
word Times
2
R
468
41129
Alarm date of over
active power demand
Year: 00–99
Month: 1–12
byte
Year,
Month
2
R
469
41130
Date: 1–31
word
Date
46A
41131
Alarm time of over
active power demand
Hour: 00–23
Minute: 00–59
byte
Hour,
Minute
2
R
46B
41132
Second: 00–59
word Second
46C
41133
Alarm status of over
reactive power
demand
0: Cleared
1: Triggered
word
2
R
46D
41134
Alarm times of over
reactive power
demand
1–255
word Times
2
R
46E
41135
Alarm date of over
reactive power
demand alarm
Year: 00–99
Month: 1–12
byte
Year,
Month
2
R
46F
41136
Date: 1–31
word
Date
470
41137
Alarm time of over
reactive power
demand
Hour: 00–23
Minute: 00–59
byte
Hour,
Minute
2
R
471
41138
Second: 00–59
word Second
Summary of Contents for DPM-C530
Page 2: ......
Page 3: ......
Page 10: ...DPM C530 Operation Manual 1 4 _1 _1 MEMO...
Page 16: ...DPM C530 Operation Manual 2 6 _2 2 4 Dimensions Front Unit mm Back Unit mm...
Page 35: ...5 1 5 Chapter 5 Parameters and Functions Table of Contents 5 1 Overview of Parameters 5 2...
Page 117: ...6 1 Chapter 6 Error Codes Table of Contents 6 1 Error Codes 6 2 6 2 Alarm Types 6 2 6...