D P M – C 5 3 0 O p e r a t i o n M a n u a l
5 - 2
_5
5.1
Overview of Parameters
Modbus
Address
Item
Range
Data
Type
Unit
Data
Size
(byte)
Read (R) /
Write (W)
Hex
Modicom
Format
0. System Parameters: 0001 – 00FF
1
40002
Present date
Year: 00–99
Month: 1–12
byte
Year,
Month
2
R/W
2
40003
Date: 1–31
Week: Sun–Sat
byte
Date,
Week
2
R/W
3
40004
Present time
Hour: 00–23
Minute: 00–59
byte
Hour,
Minute
2
R/W
4
40005
Second: 00–59
word Second
2
R/W
5
40006
Meter Constant
3200
uint P/kWh
2
R
6
40007
Meter Model
0: None
7: DMP–C530
word
2
R
7
40008
Total running time of
the meter
Day: 0–65535
uint
Day
2
R
8
40009
Hour: 00–23
Minute: 00–59
byte
Hour,
Minute
2
R
9
40010
Firmware version
0.0000 – 9.9999
uint
2
R
A
40011
Firmware release
date
Year: 00–99
Month: 1–12
byte
Year,
Month
2
R
B
40012
Date: 1–31
word
Date
2
R
C
40013
Phase rotation
0: ABC
1: CBA
word
2
R/W
Summary of Contents for DPM-C530
Page 2: ......
Page 3: ......
Page 10: ...DPM C530 Operation Manual 1 4 _1 _1 MEMO...
Page 16: ...DPM C530 Operation Manual 2 6 _2 2 4 Dimensions Front Unit mm Back Unit mm...
Page 35: ...5 1 5 Chapter 5 Parameters and Functions Table of Contents 5 1 Overview of Parameters 5 2...
Page 117: ...6 1 Chapter 6 Error Codes Table of Contents 6 1 Error Codes 6 2 6 2 Alarm Types 6 2 6...