D P M – C 5 3 0 O p e r a t i o n M a n u a l
5 - 3 6
_5
26E
40623
Date of maximum
total harmonic
distortion for phase
A voltage
Year: 00–99
Month: 1–12
byte
Year,
Month
2
R
26F
40624
Date: 1–31
word
Date
270
40625
Time of maximum
total harmonic
distortion for phase
A voltage
Hour: 00–23
Minute: 00–59
byte
Hour,
Minute
2
R
271
40626
Second: 00–59
word Second
272
40627
Maximum total
harmonic distortion for
phase B voltage
0.000 – 999.999
float
%
4
R
273
40628
274
40629
Date of maximum
total harmonic
distortion for phase
B voltage
Year: 00–99
Month: 1–12
byte
Year,
Month
2
R
275
40630
Date: 1–31
word
Date
276
40631
Time of maximum
total harmonic
distortion for phase
B voltage
Hour: 00–23
Minute: 00–59
byte
Hour,
Minute
2
R
277
40632
Second: 00–59
word Second
278
40633
Maximum total
harmonic distortion for
phase C voltage
0.000 – 999.999
float
%
4
R
279
40634
27A
40635
Date of maximum
total harmonic
distortion for phase
C voltage
Year: 00–99
Month: 1–12
byte
Year,
Month
2
R
27B
40636
Date: 1–31
word
Date
27C
40637
Time of maximum
total harmonic
distortion for phase
C voltage
Hour: 00–23
Minute: 00–59
byte
Hour,
Minute
2
R
27D
40638
Second: 00–59
word Second
2
R
27E
40639
Maximum total
harmonic distortion for
line voltage
0.000 – 999.999
float
%
4
R
27F
40640
Summary of Contents for DPM-C530
Page 2: ......
Page 3: ......
Page 10: ...DPM C530 Operation Manual 1 4 _1 _1 MEMO...
Page 16: ...DPM C530 Operation Manual 2 6 _2 2 4 Dimensions Front Unit mm Back Unit mm...
Page 35: ...5 1 5 Chapter 5 Parameters and Functions Table of Contents 5 1 Overview of Parameters 5 2...
Page 117: ...6 1 Chapter 6 Error Codes Table of Contents 6 1 Error Codes 6 2 6 2 Alarm Types 6 2 6...