D P M – C 5 3 0 O p e r a t i o n M a n u a l
5 - 6
_5
29
40042
Pickup time delay
(alarm–trigger delay)
0 – 99
word
s
2
R/W
2A
40043
Dropout setpoint
(current value
exceeding this value
clears alarm)
0.000 – 99999.999
float
A
4
R/W
2B
40044
2C
40045
Dropout time delay
(alarm–clear delay)
0 – 99
word
s
2
R/W
Alarm – Over Neutral Current
2D
40046
Alarm enable
0: Disable
1: Enable
word
2
R/W
2E
40047
Pickup setpoint
(neutral current value
exceeding this value
triggers alarm)
0.000 – 99999.999
float
A
4
R/W
2F
40048
30
40049
Pickup time delay
(alarm–trigger delay)
0 – 99
word
s
2
R/W
31
40050
Dropout setpoint
(neutral current value
below this value
clears alarm)
0.000 – 99999.999
float
A
4
R/W
32
40051
33
40052
Dropout time delay
(alarm–clear delay)
0 – 99
word
s
2
R/W
Alarm – Over Voltage L–L
34
40053
Alarm enable
0: Disable
1: Enable
word
2
R/W
35
40054
Pickup setpoint (line
voltage value
exceeding this value
triggers alarm)
0.000 – 99999.999
float
V
4
R/W
36
40055
Summary of Contents for DPM-C530
Page 2: ......
Page 3: ......
Page 10: ...DPM C530 Operation Manual 1 4 _1 _1 MEMO...
Page 16: ...DPM C530 Operation Manual 2 6 _2 2 4 Dimensions Front Unit mm Back Unit mm...
Page 35: ...5 1 5 Chapter 5 Parameters and Functions Table of Contents 5 1 Overview of Parameters 5 2...
Page 117: ...6 1 Chapter 6 Error Codes Table of Contents 6 1 Error Codes 6 2 6 2 Alarm Types 6 2 6...