C h a p t e r 5 P a r a m e t e r s a n d F u n c t i o n s
5 - 1 9
_5
1. Meter Parameters: 0100 – 01FF
100
40257
Phase A voltage
0.000 – 99999.999
float
V
4
R
101
40258
102
40259
Phase B voltage
0.000 – 99999.999
float
V
4
R
103
40260
104
40261
Phase C voltage
0.000 – 99999.999
float
V
4
R
105
40262
106
40263
Average phase
voltage
0.000 – 99999.999
float
V
4
R
107
40264
108
40265
A–B line voltage
0.000 – 99999.999
float
V
4
R
109
40266
10A
40267
B–C line voltage
0.000 – 99999.999
float
V
4
R
10B
40268
10C
40269
C–A line voltage
0.000 – 99999.999
float
V
4
R
10D
40270
10E
40271
Average line voltage 0.000 – 99999.999
float
V
4
R
10F
40272
110
40273
Phase A voltage
unbalance
0.00 – 99.99
float
%
4
R
111
40274
112
40275
Phase B voltage
unbalance
0.00 – 99.99
float
%
4
R
113
40276
114
40277
Phase C voltage
unbalance
0.00 – 99.99
float
%
4
R
115
40278
116
40279
Phase voltage
0.00 – 99.99
float
%
4
R
Summary of Contents for DPM-C530
Page 2: ......
Page 3: ......
Page 10: ...DPM C530 Operation Manual 1 4 _1 _1 MEMO...
Page 16: ...DPM C530 Operation Manual 2 6 _2 2 4 Dimensions Front Unit mm Back Unit mm...
Page 35: ...5 1 5 Chapter 5 Parameters and Functions Table of Contents 5 1 Overview of Parameters 5 2...
Page 117: ...6 1 Chapter 6 Error Codes Table of Contents 6 1 Error Codes 6 2 6 2 Alarm Types 6 2 6...