D P M - C 5 3 0 O p e r a t i o n M a n u a l
6 - 2
_6
6.1
Error Codes
When an error occurs during operation, the power monitor sends an error code through Modbus. The following
table lists the error codes and causes.
Error Code
Name
Description
0x01
Illegal function
Incorrect function code
0x02
Illegal data address
Incorrect data address to read or write
0x03
Illegal data value
Incorrect data format (for example, data length)
0x04
Slave device failure
Slave cannot execute the command.
6.2
Alarm Types
The power meter supports 29 types of alarms. You can activate the alarm in the registers 0x1F–0xDD. When
an alarm is triggered, the data (such as alarm type and alarm triggered time) are stored in registers
0xB700–0xC0C3. The following table lists the details and descriptions for the alarm types.
Number
Alarm Type
Description
1
Over Current
The measured current exceeds the setting value.
2
Under Current
The measured current is below the setting value.
3
Over Neutral Current
The measured neutral current exceeds the setting value.
4
Over Voltage LL
The measured line voltage exceeds the setting value.
5
Under Voltage LL
The measured line voltage is below the setting value.
6
Over Voltage LN
The measured phase voltage exceeds the setting value.
7
Under Voltage LN
The measured phase voltage is below the setting value.
8
Over Volt Unbalance
The measured voltage unbalance exceeds the setting value.
9
Over AMP Unbalance
The measured current unbalance is below the setting value.
10
Over Active power
The measured total active power exceeds the setting value.
11
Over Reactive Power
The measured total reactive power exceeds the setting value.
12
Over Apparent Power
The measured total apparent power exceeds the setting value.
13
LEAD PF
The leading power factor is below the setting value.
14
Lag PF
The lagging power factor is below the setting value.
15
Lead DPF
The leading power factor demand is below the setting value.
Summary of Contents for DPM-C530
Page 2: ......
Page 3: ......
Page 10: ...DPM C530 Operation Manual 1 4 _1 _1 MEMO...
Page 16: ...DPM C530 Operation Manual 2 6 _2 2 4 Dimensions Front Unit mm Back Unit mm...
Page 35: ...5 1 5 Chapter 5 Parameters and Functions Table of Contents 5 1 Overview of Parameters 5 2...
Page 117: ...6 1 Chapter 6 Error Codes Table of Contents 6 1 Error Codes 6 2 6 2 Alarm Types 6 2 6...