C h a p t e r 5 P a r a m e t e r s a n d F u n c t i o n s
5 - 7
_5
37
40056
Pickup time delay
(alarm–trigger delay)
0 – 99
word
s
2
R/W
38
40057
Dropout setpoint (line
voltage value below
this value clears
alarm)
0.000 – 99999.999
float
V
4
R/W
39
40058
3A
40059
Dropout time delay
(alarm–clear delay)
0 – 99
word
s
2
R/W
Alarm – Under Voltage L–L
3B
40060
Alarm enable
0: Disable
1: Enable
word
2
R/W
3C
40061
Pickup setpoint (line
voltage value below
this value triggers
alarm)
0.000 – 99999.999
float
V
4
R/W
3D
40062
3E
40063
Pickup time delay
(alarm–trigger delay)
0 – 99
word
s
2
R/W
3F
40064
Dropout setpoint (line
voltage value
exceeding this value
clears alarm)
0.000 – 99999.999
float
V
4
R/W
40
40065
41
40066
Dropout time delay
(alarm–clear delay)
0 – 99
word
s
2
R/W
Alarm – Over Voltage L–N
42
40067
Alarm enable
0: Disable
1: Enable
word
2
R/W
43
40068
Pickup setpoint
(phase voltage value
exceeding this value
triggers alarm)
0.000 – 99999.999
float
V
4
R/W
44
40069
Summary of Contents for DPM-C530
Page 2: ......
Page 3: ......
Page 10: ...DPM C530 Operation Manual 1 4 _1 _1 MEMO...
Page 16: ...DPM C530 Operation Manual 2 6 _2 2 4 Dimensions Front Unit mm Back Unit mm...
Page 35: ...5 1 5 Chapter 5 Parameters and Functions Table of Contents 5 1 Overview of Parameters 5 2...
Page 117: ...6 1 Chapter 6 Error Codes Table of Contents 6 1 Error Codes 6 2 6 2 Alarm Types 6 2 6...