C h a p t e r 5 P a r a m e t e r s a n d F u n c t i o n s
5 - 1 3
_5
8A
40139
factor value below this
value triggers alarm)
8B
40140
Pickup time delay
(alarm–trigger delay)
0 – 99
word
s
2
R/W
8C
40141
Dropout setpoint (total
displacement power
factor value
exceeding this value
clears alarm)
0.00000 – 1.00000
float
4
R/W
8D
40142
8E
40143
Dropout time delay
(alarm–clear delay)
0 – 99
word
s
2
R/W
Alarm – Over Current Demand
8F
40144
Alarm enable
0: Disable
1: Enable
word
2
R/W
90
40145
Pickup setpoint
(current demand
value exceeding this
value triggers alarm)
0.000 – 99999.999
float
A
4
R/W
91
40146
92
40147
Pickup time delay
(alarm–trigger delay)
0 – 99
word
s
2
R/W
93
40148
Dropout setpoint
(current demand
value below this value
clears alarm)
0.000 – 99999.999
float
A
4
R/W
94
40149
95
40150
Dropout time delay
(alarm–clear delay)
0 – 99
word
s
2
R/W
Alarm – Over Active Power Demand
96
40151
Alarm enable
0: Disable
1: Enable
word
2
R/W